– 68 –
Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[H06]
[Low pressure(PS) lowering trouble]
When cooling, the indoor unit
fan operate normally?
Trouble part
repair
Is indoor fan motor
relation normal?
1. Connector connection
2. Capacitors
3. Fan motor
NO
NO
Is outdoor unit fan
motor relation normal?
1. Connector connection
2. Fan motor
NO
Trouble part
repair
NO
Cleaning
YES
Cleaning
YES
Correct wiring
NO
NO
Replace indoor P.C. board
YES
YES
Replace fan motor IPDU
P.C. board
YES
Is there an outdoor unit
heat exchanger clogging?
NO
Is there indoor unit filter
or heat exchanger
clogging?
NO
When heating, the
outdoor unit fan operate
normally?
Is the service valve
of the outdoor unit fully
open?
YES
Is the characteristics of
the low pressure
sensor normal?
YES
Is the SV2 bypass circuit
normal?
YES
YES
Service valve fully open
NO
Replace low pressure sensor
NO
Correction of SV2 bypass circuit
Check the outdoor
unit wiring
After confirming that there is clogging or piping
breakage, determine the amount of refrigerant
and add refrigerant.
Refrigerant shortage,
clogging, broken pipe.
YES
Is the wiring correct?