– 66 –
Check
code
Outdoor
LED display
Check and troubleshooting
(Item without special mention Indicates part of outdoor unit.)
[H01]
[Compressor break down]
Is power supply voltage normal?
AC342 to 457V
NO
Correct power supply line.
NO
Check wire connection
and correct it.
YES
Is wire connection correct?
Compressor lead
(P.C. board side, Compressor side),
Reactor lead, Power supply lead
YES
YES
Remove and improve
the cause of overload.
Replace compressor IPDU P.C. board.
* When replacing Compressor IPDU P.C.board,
replace the fuse.
Replace compressor IPDU P.C. board.
* When replacing Compressor IPDU P.C.board,
replace the fuse.
Does an abnormal overload happen?
NO
[H02]
[Compressor lock]
Is power supply voltage normal?
AC342 to 457V
NO
Correct power supply line.
NO
Compressor lock
→
Replace
Check wire connection
and correct it.
YES
Is wire connection correct?
Compressor lead
(P.C. board side, Compressor side),
Reactor lead, Power supply lead
YES
Is compressor under correct conditions?
NO
YES
NO
NO
Check TE, TS sensors
and PMV.
Failure
→
Replace
Is there refrigerant stagnation?
YES
Does PMV correctly operate?
YES