Domestic Hot Water Heat Pump Service Manual
47
9.4.3 Er Evap
– Evaporator temperature error analysis
Er Evap is activated in the case of a possible leak in refrigerant; the control is activated if:
BBT2>BBT1 -2k
The compressor is ON
The duration of the temperature difference is longer than one hour.
9.4.4 Er H Evap
– High evaporator temperature error analysis
Er H Evap (high evaporator temperature) is activated under the following conditions:
Compressor in ON
BBT2 > Evaporator Temperature Max (D11 Evaporator temp max, factory setting 30°C)
The control is active 10 minutes after compressor starts and is activated after 5 minutes.
Are the BBT1 & BT2
sensors operating correctly
with no defects?
No
Complete steps
from 8.4.1
Is there a lack of
refrigerant?
Yes
Yes
Check for leaks.
Recharge with refrigerant.
Are the BBT1 & BT2
sensors operating correctly
with no defects?
No
Complete steps
from 8.4.1
Is there a lack of
refrigerant?
Yes
Yes
Check for leaks.
Recharge with refrigerant.