Domestic Hot Water Heat Pump Service Manual
48
9.4.5 Er C Evap
– Low evaporator temperature error analysis
The Low evaporation temperature error occurs if:
-29 < BBT2 < -25
9.4.6 Er Filter
– Change filter error analysis
Filter error occurs if D30 (Filter Timer) is ON and the time of the D31 (Filter Timer Time) has
elapsed since the last time the filter timer has been reset in D32 (Filter Reset).
9.5
Resetting of error code & BACK-UP mode
Once the cause of the error has been corrected or a repair has been completed the DHW-HP can
be reset to normal operation.
To reset the error code a power cycle musty be established. Switch the electrical supply to the
DHW-HP OFF and then back ON after approximately 30 seconds.
Once the power has been reset, using the Up & Down arrow buttons on the remote controller,
select the operation mode required, i.e. AUTO mode.
The unit should now operate correctly.
The filter timer has elapsed
Yes
Replace or clean
filters
Is the fan motor operating
correctly?
No
Yes
Is the fan motor
connected to
the PC board?
No
Connect fan motor
to PC board
Does the fan
motor turn?
No
Replace the fan
motor
Is the fan
speed set too
high?
No
Reduce the fan
speed
Is the BT temperature
sensor(s) positioned and
connected correctly?
No
Yes
Is the sensor(s)
correctly
positioned?
No
Move sensor(s) into
correct position
Is the sensor(s)
connected to
the PC board?
No
Connect sensor(s)
to the PC board
Are the BBT1 & BT2
sensors operating correctly
with no defects?
No
Complete steps
from 8.4.1
Yes
Is the inlet temperature too
low
Yes
Increase the
minimum air
temperature from
D7