Domestic Hot Water Heat Pump Service Manual
56
Code
Set point
name
Description
Range
Factory
setting
D12
BACK-
UP Temp
The water temperature at which the unit stops the backup mode with only
the electric heater.
0-65
35
D13
Legionella
The legionella function can be activated. The legionella function does not
switch the heat pump on, but just continues the heat up cycle to a higher
temperature D14 (Legionella T). The legionella operation works only with
the heat pump until 60°C. The remaining temperature lift is accomplished
with the electric heater alone.
OFF/ON
OFF
D14
Legionella
Temp
The legionella temperature set point can be regulated.
60-65
60
D15
Legionella
date
The legionella week day can be set
Monday/
Sunday
Sunday
D16
Forced
operation
The forced operation of the heat pump can be activated here. The heat
pump starts even if there is no demand for hot water. When the maximum
temperature allowed by the heat pump is reached the unit will stop. This
function is to use for testing purposes. It becomes OFF again after one
heat up cycle is completed.
OFF/ON
OFF
D17
Low Tariff
weekday
The start and stop time of the low electricity tariff period for weekdays.
Three periods can be selected.
0-23
0-23
0-23
0
0
0
D18
Low Tariff
weekend
The start and stop time of the low electricity tariff period for weekends.
Three periods can be selected.
0-23
0-23
0-23
0
0
0
D19
Light
Saving
Time
Light Saving Time can be deactivated.
OFF/ON
ON
D20
PV min
Voltage HP
The minimum voltage (V) required to start the HP when the PV function is
active.
0-10
0
D21
PV min
Voltage EL
The minimum voltage (V) required to start the electric heater when the
PV function is active.
0-10
0
D22
PV min
time
The minimum time (minutes) at which the input voltage from the PV panel
should be above the set point D20/D21 (PV min Voltage HP/EL) in order to
start the electric heater or heat pump when the PV function is active D22
also regulates the minimum heat pump operational time when started by
the PV function.
1-120
15
D23
Solar Temp
max
The maximum allowed temperature (°C) in the solar collector.
55-89
89
D24
Solar DT
min
The minimum temperature (°C) difference between solar collector and
tank.
1-5
5
D25
Floor Temp
start
The temperature (°C) that needs to be in the tank to allow the floor function
to be active with hysteresis of 1K.
25-45
35
D26
Extra
function
The desired extra function is selected here. The possible functions are
Solar, Floor or Cooling. Once the function is activated, move to the function
menu and adjust the set point as desired.
OFF/ Solar/
Floor/
Cooling
OFF