Setting
The setting elements necessary for the breaker failure protection and its setting ranges are as
follows:
Element Range
Step Default Remarks
OCBF
0.5
−
10.0A
0.1A 4.0A Overcurrent
setting
(0.1
−
2.0A
0.1A 0.8A)
(*)
TBF1
50
−
500ms
1ms 150ms Retrip
timer
TBF2
50
−
500ms
1ms
200ms
Adjacent breaker trip timer
[BFEXT] ON/OFF
OFF
External
start
[BF1] T/TOC/OFF
OFF Retrip
mode
[BF2]
ON/OFF
OFF
Adjacent breaker trip
(*)
Current values shown in parentheses are in the case of 1A rating. Other current values are in
the case of 5A rating.
The overcurrent element OCBF checks that the breaker has opened and the current has
disappeared. Therefore, since it is allowed to respond to the load current, it can be set from 10 to
200% of the rated current.
The settings of TBF1 and TBF2 are determined by the opening time of the original breaker (Tcb
in Figure 2.7.2) and the reset time of the overcurrent element (Toc in Figure 2.7.2). The timer
setting example when using retrip can be obtained as follows.
Setting of TBF1 = Breaker opening time + OCBF reset time + Margin
= 40ms + 10ms + 20ms
=
70ms
Setting of TBF2 = TBF1 + Output relay operating time + Breaker opening time +
OCBF reset time + Margin
= 70ms + 10ms + 40ms + 10ms + 10ms
=
140ms
If retrip is not used, the setting of TBF2 can be the same as that of TBF1.
Содержание GRL100-101A
Страница 8: ... 7 6 F 2 S 0 8 3 5 6 7 4 Resumption of Service 220 6 7 5 Storage 220 7 Putting Relay into Service 221 ...
Страница 223: ... 222 6 F 2 S 0 8 3 5 ...
Страница 228: ... 227 6 F 2 S 0 8 3 5 Appendix B Signal List ...
Страница 256: ... 255 6 F 2 S 0 8 3 5 Appendix C Variable Timer List ...
Страница 258: ... 257 6 F 2 S 0 8 3 5 Appendix D Binary Output Default Setting List ...
Страница 269: ... 268 6 F 2 S 0 8 3 5 ...
Страница 270: ... 269 6 F 2 S 0 8 3 5 Appendix E Details of Relay Menu ...
Страница 279: ... 278 6 F 2 S 0 8 3 5 ...
Страница 288: ... 287 6 F 2 S 0 8 3 5 Appendix G Typical External Connection ...
Страница 326: ... 325 6 F 2 S 0 8 3 5 Appendix J Return Repair Form ...
Страница 330: ... 329 6 F 2 S 0 8 3 5 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Страница 331: ... 330 6 F 2 S 0 8 3 5 ...
Страница 332: ... 331 6 F 2 S 0 8 3 5 Appendix K Technical Data ...
Страница 343: ... 342 6 F 2 S 0 8 3 5 ...
Страница 344: ... 343 6 F 2 S 0 8 3 5 Appendix L Symbols Used in Scheme Logic ...
Страница 347: ... 346 6 F 2 S 0 8 3 5 ...
Страница 348: ... 347 6 F 2 S 0 8 3 5 Appendix M Multi phase Autoreclose ...
Страница 351: ... 350 6 F 2 S 0 8 3 5 ...
Страница 352: ... 351 6 F 2 S 0 8 3 5 Appendix N Data Transmission Format ...
Страница 358: ... 357 6 F 2 S 0 8 3 5 Appendix O Example of DIF and DIFG Setting ...
Страница 360: ... 359 6 F 2 S 0 8 3 5 Appendix P Programmable Reset Characteristics and Implementation of Thermal Model to IEC60255 8 ...
Страница 364: ... 363 6 F 2 S 0 8 3 5 Appendix Q IEC60870 5 103 Interoperability ...
Страница 377: ... 376 6 F 2 S 0 8 3 5 ...
Страница 378: ... 377 6 F 2 S 0 8 3 5 Appendix R Failed Module Tracing and Replacement ...
Страница 384: ... 383 6 F 2 S 0 8 3 5 Appendix S PLC Setting Sample ...
Страница 386: ... 385 6 F 2 S 0 8 3 5 Appendix T Ordering ...
Страница 392: ......