the value at which the element operates. Check that the measured value is within
±
5% of the
setting.
Synchronism check element SYN1
•
Press 4 (= Logic circuit) on the "Test" screen to display the "Logic circuit" screen.
•
Enter a signal number for the TermA line to be observed at monitoring jack A and press the
ENTER key.
•
Apply a three-phase rated voltage and a single-phase rated voltage as shown in Figure
6.5.1.8.
Voltage check:
•
Set the three-phase voltage to any value over the SY1OV setting. (The default setting of
SY1OV is 51V.)
Whilst keeping Vr in-phase with Va, lower the single-phase voltage Vr from the rated value.
Measure the voltage at which the element operates. Check that the measured voltage is within
±
5% of the SY1UV setting.
•
Further lower Vr and measure the voltage at which the element resets. Check that the
measured voltage is within
±
5% of the SY1OV setting.
Phase angle check:
•
Set
Va and Vr to any value between the SY1OV and SY1UV settings keeping Va in-phase
with Vr. Then the SYN1 element operates.
•
Shift the angle of Vr away from that of Va, and measure the angle at which the element resets.
•
Check that the measured angle is within
±
5° of the SY1
θ
setting. (The default setting of SY1
θ
is 30°.)
•
Change
Va and Vr, and repeat the above.
Synchronism check element SYN2
•
Apply single-phase rated voltage to terminals 17 and 18 as shown with broken lines in Figure
6.5.1.8 and set the scheme switch "3PH-VT" to "Line". The test can be performed taking the
same steps as testing SYN1.
Содержание GRL100-101A
Страница 8: ... 7 6 F 2 S 0 8 3 5 6 7 4 Resumption of Service 220 6 7 5 Storage 220 7 Putting Relay into Service 221 ...
Страница 223: ... 222 6 F 2 S 0 8 3 5 ...
Страница 228: ... 227 6 F 2 S 0 8 3 5 Appendix B Signal List ...
Страница 256: ... 255 6 F 2 S 0 8 3 5 Appendix C Variable Timer List ...
Страница 258: ... 257 6 F 2 S 0 8 3 5 Appendix D Binary Output Default Setting List ...
Страница 269: ... 268 6 F 2 S 0 8 3 5 ...
Страница 270: ... 269 6 F 2 S 0 8 3 5 Appendix E Details of Relay Menu ...
Страница 279: ... 278 6 F 2 S 0 8 3 5 ...
Страница 288: ... 287 6 F 2 S 0 8 3 5 Appendix G Typical External Connection ...
Страница 326: ... 325 6 F 2 S 0 8 3 5 Appendix J Return Repair Form ...
Страница 330: ... 329 6 F 2 S 0 8 3 5 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Страница 331: ... 330 6 F 2 S 0 8 3 5 ...
Страница 332: ... 331 6 F 2 S 0 8 3 5 Appendix K Technical Data ...
Страница 343: ... 342 6 F 2 S 0 8 3 5 ...
Страница 344: ... 343 6 F 2 S 0 8 3 5 Appendix L Symbols Used in Scheme Logic ...
Страница 347: ... 346 6 F 2 S 0 8 3 5 ...
Страница 348: ... 347 6 F 2 S 0 8 3 5 Appendix M Multi phase Autoreclose ...
Страница 351: ... 350 6 F 2 S 0 8 3 5 ...
Страница 352: ... 351 6 F 2 S 0 8 3 5 Appendix N Data Transmission Format ...
Страница 358: ... 357 6 F 2 S 0 8 3 5 Appendix O Example of DIF and DIFG Setting ...
Страница 360: ... 359 6 F 2 S 0 8 3 5 Appendix P Programmable Reset Characteristics and Implementation of Thermal Model to IEC60255 8 ...
Страница 364: ... 363 6 F 2 S 0 8 3 5 Appendix Q IEC60870 5 103 Interoperability ...
Страница 377: ... 376 6 F 2 S 0 8 3 5 ...
Страница 378: ... 377 6 F 2 S 0 8 3 5 Appendix R Failed Module Tracing and Replacement ...
Страница 384: ... 383 6 F 2 S 0 8 3 5 Appendix S PLC Setting Sample ...
Страница 386: ... 385 6 F 2 S 0 8 3 5 Appendix T Ordering ...
Страница 392: ......