Relay and Protection Scheme Setting Sheet
Default Setting of Relay Series(5A rating / 1A rating)
№
Name
Range
Units
Contents
NO-ARC,NO-FD
1CB-ARC,NO-FD
2CB-ARC,NO-FD
1CB-ARC,FD
2CB-ARC,FD
1CB-ARC,NO-FD
User
2TERM 3TERM
2TERM
3TERM
2TERM
3TERM
2TERM
3TERM
2TERM
3TERM
2TERM
3TERM
Settiing
5A rating
1A rating
101, 102 111, 112 201
202
211
212
301
302
312
401
411
501
503
511
513
204
206
214
216
126
EFI
EFI
0.5 - 5.0
0.10 - 1.00
A
IDMT earth fault OC element
5.0 / 1.0
5.0 / 1.0
127
TEFI
0.05 - 1.00
-
ditto
0.50
0.50
128
TEFIR
0.0 - 10.0
s
EF definite time reset delay
0.0
0.0
129 Thermal
THM
2.0 - 10.0
0.40 - 2.00
A
Thermal overload setting
5.0 / 1.00
--
5.0 / 1.00
130
THMIP
0.0 - 5.0
0.00 - 1.00
A
Prior load setting
0.0 / 0.00
--
0.0 / 0.00
131
TTHM
0.5 - 300.0
min Thermal Time Constant
10.0
--
10.0
132
THMA
50 - 99
%
Thermal alarm setting
80
--
80
133
OCCHK
0.5 - 5.0
0.10 - 1.00
A
Minimum current for
θ
calc.
0.5 / 0.10
0.5 / 0.10
134
HYS
θ
1 - 5
deg
Hysteresis of phase difference
1
1
135
CFID
0.25 - 5.00
0.05 - 1.00
A
Id revel of CTF scheme
--
0.50 / 0.10
0.50 / 0.10
136
CFUV
20 - 60
V
UV revel of CTF scheme
--
20
20
137
CFDV
1 - 10
%
UVD revel of CTF scheme
--
7
7
138
CFOVG
0.1 - 10.0
V
Zero pahse overvoltage of CTF
scheme
--
1.0
1.0
139 Autoreclose mode
(Off) - Disable - SPAR - TPAR -
SPAR&TPAR - MPAR2 - MPAR3 -
EXT1P - EXT3P - EXTMP
-
Autoreclosing mode
--
SPAR&TPAR
SPAR&TPAR
140
ARC-CB
ONE - O1 - 02 - L1 - L2
-
ARC mode for 1.5CB system
--
--
L1
--
L1
--
141
ARC-EXT
Off - On
-
ARC initiated by ext. trip
--
Off
Off
142
ARCDIFG
Off - On
-
ARC by DIFG trip
--
Off
Off
143
ARC-BU
Off - On
-
ARC by back-up trip
--
Off
Off
144 VCHK
1CB
Off - LB - DB - SY
-
TPAR condition
--
LB
-- (SY)
LB
-- (SY)
LB
2CB
Off - LB1 - LB2 - DB - SY
--
--
LB1
--
LB1
--
145
ARC-SM
Off - S2 - S3 - S4
-
Multi. shot ARC mode
--
Off
Off
146
ARC-CCB
Off - TPAR - MPAR
-
Center CB ARC mode at multi-
phase ARC mode selected
--
--
MPAR
--
MPAR
--
147
ARC-SUC
Off - On
-
ARC success reset
--
Off
Off
148
MA-NOLK
FT - T - S+T
-
Multi ARC NO-LINK condition
--
FT
FT
149
VTPHSEL
A - B - C
-
VT phase selection
--
A
A
150
VT-RATE
PH/G - PH/PH
-
VT rating
--
PH/G
PH/G
151
3PH-VT
Bus - Line
-
3ph. VT location
--
Line
Line
152
UARCSW
P1 - P2 - P3
-
User ARC switch
--
P1
P1
153
TEVLV
0.01 - 10.00
s
Dead timer reset timing
--
0.30
0.30
154
TRDY1
5 - 300
s
Reclaim timer
--
60
60
155
TSPR1
0.01 - 10.00
s
SPAR dead line timer
--
0.80
0.80
156
TTPR1
0.01 - 100.00
s
TPAR dead line timer
--
0.60
0.60
157
TMPR1
0.01 - 10.00
s
MPAR dead time timer
--
0.80
0.80
158
TRR
0.01 - 100.00
s
ARC reset timer
--
2.00
2.00
159
TW1
0.1 - 10.0
s
ARC reset timer
--
0.2
0.2
160
TRDY2
5 - 300
s
Reclaim timer
--
--
60
--
60
--
161
TSPR2
0.01 - 10.00
s
SPAR dead line timer
--
--
0.80
--
0.80
--
162
TTPR2
0.1 - 10.0
s
ARC timing for follower CB
--
--
0.1
--
0.1
--
163
TMPR2
0.01 - 10.00
s
MPAR dead time timer
--
--
0.80
--
0.80
--
164
TW2
0.1 - 10.0
s
ARC reset timer
--
--
0.2
--
0.2
--
165
TS2
5.0 - 300.0
s
Multi. shot dead timer
--
20.0
20.0
166
TS2R
5.0 - 300.0
s
Multi. shot reset timer
--
30.0
30.0
167
TS3
5.0 - 300.0
s
Multi. shot dead timer
--
20.0
20.0
168
TS3R
5.0 - 300.0
s
Multi. shot reset timer
--
30.0
30.0
169
TS4
5.0 - 300.0
s
Multi. shot dead timer
--
20.0
20.0
170
TS4R
5.0 - 300.0
s
Multi. shot reset timer
--
30.0
30.0
171
TSUC
0.1 - 10.0
s
ARC success reset timer
--
3.0
3.0
172
OVB
10 - 150
V
OV element
--
51
51
173
UVB
10 - 150
V
UV element
--
13
13
174
OVL1
10 - 150
V
OV element
--
51
51
175
UVL1
10 - 150
V
UV element
--
13
13
176
SY1UV
10 - 150
V
Synchro. check (UV)
--
83
83
177
SY1OV
10 - 150
V
Synchro. check (OV)
--
51
51
178
SY1
θ
5 - 75
deg Synchro. check (ph. diff.)
--
30
30
179
TSYN1
0.01 - 10.00
s
Synchronism check timer
--
1.00
1.00
180
TDBL1
0.01 - 1.00
s
Voltage check timer
--
0.05
0.05
181
TLBD1
0.01 - 1.00
s
Voltage check timer
--
0.05
0.05
Содержание GRL100-101A
Страница 8: ... 7 6 F 2 S 0 8 3 5 6 7 4 Resumption of Service 220 6 7 5 Storage 220 7 Putting Relay into Service 221 ...
Страница 223: ... 222 6 F 2 S 0 8 3 5 ...
Страница 228: ... 227 6 F 2 S 0 8 3 5 Appendix B Signal List ...
Страница 256: ... 255 6 F 2 S 0 8 3 5 Appendix C Variable Timer List ...
Страница 258: ... 257 6 F 2 S 0 8 3 5 Appendix D Binary Output Default Setting List ...
Страница 269: ... 268 6 F 2 S 0 8 3 5 ...
Страница 270: ... 269 6 F 2 S 0 8 3 5 Appendix E Details of Relay Menu ...
Страница 279: ... 278 6 F 2 S 0 8 3 5 ...
Страница 288: ... 287 6 F 2 S 0 8 3 5 Appendix G Typical External Connection ...
Страница 326: ... 325 6 F 2 S 0 8 3 5 Appendix J Return Repair Form ...
Страница 330: ... 329 6 F 2 S 0 8 3 5 Customer Name Company Name Address Telephone No Facsimile No Signature ...
Страница 331: ... 330 6 F 2 S 0 8 3 5 ...
Страница 332: ... 331 6 F 2 S 0 8 3 5 Appendix K Technical Data ...
Страница 343: ... 342 6 F 2 S 0 8 3 5 ...
Страница 344: ... 343 6 F 2 S 0 8 3 5 Appendix L Symbols Used in Scheme Logic ...
Страница 347: ... 346 6 F 2 S 0 8 3 5 ...
Страница 348: ... 347 6 F 2 S 0 8 3 5 Appendix M Multi phase Autoreclose ...
Страница 351: ... 350 6 F 2 S 0 8 3 5 ...
Страница 352: ... 351 6 F 2 S 0 8 3 5 Appendix N Data Transmission Format ...
Страница 358: ... 357 6 F 2 S 0 8 3 5 Appendix O Example of DIF and DIFG Setting ...
Страница 360: ... 359 6 F 2 S 0 8 3 5 Appendix P Programmable Reset Characteristics and Implementation of Thermal Model to IEC60255 8 ...
Страница 364: ... 363 6 F 2 S 0 8 3 5 Appendix Q IEC60870 5 103 Interoperability ...
Страница 377: ... 376 6 F 2 S 0 8 3 5 ...
Страница 378: ... 377 6 F 2 S 0 8 3 5 Appendix R Failed Module Tracing and Replacement ...
Страница 384: ... 383 6 F 2 S 0 8 3 5 Appendix S PLC Setting Sample ...
Страница 386: ... 385 6 F 2 S 0 8 3 5 Appendix T Ordering ...
Страница 392: ......