H7 ASD Operation Manual
77
OUT7 Off Delay
Program
⇒
Terminal Selection Parameters
⇒
Output Terminal Delays
⇒
OUT7
This parameter delays the opening of the OUT7 output terminals by the
programmed value (see waveforms at
).
The delay may be increased to allow the devices that are connected to OUT7 to
respond.
Direct Access Number — F166
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Motor #2 Base Frequency
Program
⇒
Motor Parameters
⇒
Motor Set #2
The Motor #2 Base Frequency setting is the frequency at which the output
voltage of the ASD reaches its maximum setting. The #2 Maximum Output
Voltage is set at
.
This parameter is used only when the parameters for motor set #2 are
configured and selected. Motor set #2 may be selected by a properly configured
input terminal.
For proper motor operation, the Base Frequency should be set for the name-
plated frequency of the motor.
Direct Access Number — F170
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 25.0
Maximum — 400.0
Units — Hz
Motor #2 Max Output Voltage
Program
⇒
Motor Parameters
⇒
Motor Set #2
The Motor #2 Maximum Output Voltage is the Motor #2 output voltage at
the Base Frequency (
). Regardless of the programmed value, the output
voltage cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the Supply Voltage Compensation setting (
).
This parameter is used only when the parameters for motor set #2 are
configured and selected. Motor set #2 may be selected by a properly configured
input terminal.
Direct Access Number — F171
Parameter Type — Numerical
Factory Default — (drive dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — 600.0
Units — Volts
Motor #2 Torque Boost
Program
⇒
Motor Parameters
⇒
Motor Set #2
The Motor #2 Torque Boost function is used to increase the low frequency
torque for high inertia loads by increasing the output voltage at frequencies
below ½ of the #2 Base Frequency setting (
).
See parameter
(Motor #1 Torque Boost) for an explanation of torque
boost.
This parameter is used only when the parameters for motor set #2 are
configured and selected. Motor set #2 may be selected by a properly configured
input terminal.
Direct Access Number — F172
Parameter Type — Numerical
Factory Default — (drive dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — %
www
. ElectricalPartManuals
. com
Содержание Adjustable Speed Drive H7 Series
Страница 198: ...H7 ASD Operation Manual Appendix A 191 Figure 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 199: ...192 Appendix A H7 ASD Operation Manual Figure 24 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 201: ...194 Appendix A H7 ASD Operation Manual Figure 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...