86
H7 ASD Operation Manual
VI/II Torque Reference Setpoint #2 (%)
Program
⇒
Torque Setting Parameters
⇒
Setpoints
⇒
VI/II
This parameter is used to set the gain and bias of the VI/II input terminals when
either terminal is used as the control input while operating in the Torque
Control mode.
This is accomplished by establishing an associated V/f output pattern for a
given VI/II input level and motor load.
for further information on this setting.
This parameter sets Torque Reference Setpoint #2 (%) and is the output
torque value that is associated with the setting of
F203
. This value is entered as
0 to 250% of the rated torque.
Direct Access Number — F206
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 250.0
Units — %
Frequency Mode #2
Program
⇒
Fundamental Parameters
⇒
Standard Mode Selection
This parameter selects the source of the frequency command signal to be used
as Frequency Mode #2 in the event that Frequency Mode #1 is disabled or if
Frequency Mode #2 is set up as the primary control parameter. See
for
additional information on this setting.
Settings:
Use VI/II
Use RR
Use RX
Use Option Card RX2
Use LED Keypad Option
Use Binary/BCD Input
Use EOI
Use RS232/485
Use Communication Card
Use Motorized Pot. Simulation
Use Pulse Input Option
Direct Access Number — F207
Parameter Type — Selection List
Factory Default — VI/II
Changeable During Run — Yes
Mode #1/#2 Switching Frequency
Program
⇒
Fundamental Parameters
⇒
Standard Mode Selection
⇒
Mode #1/#2 Switching Frequency
This parameter sets the threshold frequency that will be used in
to
determine if Frequency Source #1 or #2 will control the output of the ASD.
for additional information on this setting.
Direct Access Number — F208
Parameter Type — Numerical
Factory Default — 1.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — Max. Freq. (
)
Units — Hz
www
. ElectricalPartManuals
. com
Содержание Adjustable Speed Drive H7 Series
Страница 198: ...H7 ASD Operation Manual Appendix A 191 Figure 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 199: ...192 Appendix A H7 ASD Operation Manual Figure 24 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 201: ...194 Appendix A H7 ASD Operation Manual Figure 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...