Table 6 . Discrete Input Terminal Assignment Selections and Descriptions.
0 — Unassigned — No operation.
1 — F — Enables the Forward operation command.
2 — R — Enables the Reverse operation command.
3 — ST — Enables the Forward and Reverse operation commands (maybe disabled at
F103
).
4 — RES — Resets the device and any incurred faults.
5 — S1 — Preset Speed Command 1 is used as the LSB of the 4-bit nibble that is used to select a Preset Speed.
6 — S2 — Preset Speed Command 2 is used as the second bit of the 4-bit nibble that is used to select a Preset Speed.
7 — S3 — Preset Speed Command 3 is used as the third bit of the 4-bit nibble that is used to select a Preset Speed.
8 — S4 — Preset Speed Command 4 is used as the MSB of the 4-bit nibble that is used to select a Preset Speed.
9 — Jog — Jog is the term used to describe turning on the motor for small increments of time and is used when precise
positioning of motor-driven equipment is required. This terminal activates a Jog for the duration of activation. The Jog
settings may be configured at
and
.
10 — Emergency Off — Terminates the output signal from the drive and may apply a brake. The braking method may be
.
11 — DC Braking — The drive outputs a DC current that is injected into the windings of the motor to quickly brake the
motor.
12 — Accel/Decel 1, 2 Switching — Acceleration and Deceleration control may be switched from the #1 profile to the #2
profile during a multiple-accel/decel profile configuration by connecting this terminal to CC.
13 — Accel/Decel 3, 4 Switching — Acceleration and Deceleration control may be switched from the #3 profile to the #4
profile during a multiple-accel/decel profile configuration by connecting this terminal to CC.
14 — Motor 1, 2 Switching — Motor control may be switched from the Motor #1 profile to the Motor #2 profile during a
multiple-motor profile configuration by connecting this terminal to CC.
15 — Motor 3, 4 Switching — Motor control may be switched from the Motor #3 profile to the Motor #4 profile during a
multiple-motor profile configuration by connecting this terminal to CC.
16 — Torque Limit 1, 2 Switching — Torque control may be switched from the Torque Limit #1 profile to the Torque Limit
#2 profile during a multiple-profile configuration by connecting this terminal to CC.
17 — Torque Limit 3, 4 Switching — Torque control may be switched from the Torque Limit #3 profile to the Torque Limit
#4 profile during a multiple-profile configuration by connecting this terminal to CC.
18 — Control Off — Connecting this terminal to CC turns off PID control.
19 — Pattern #1 — Connecting this terminal to CC initiates the Pattern #1 Pattern Run.
20 — Pattern #2 — Connecting this terminal to CC initiates the Pattern #2 Pattern Run.
21 — Pattern #3 — Connecting this terminal to CC initiates the Pattern #3 Pattern Run.
22 — Pattern #4 — Connecting this terminal to CC initiates the Pattern #4 Pattern Run.
23 — Pattern Continue — Continues with the last Pattern Run from its stopping point when connected to CC.
24 — Pattern Trigger — This function is used to sequentially initiate each Preset Speed of a Pattern Run with each
connection to CC.
25 — Forced Jog Forward — This setting initiates a Forced Forward Jog when connected to CC. The Forced Forward
Jog command provides a forward-run signal so long as this terminal is connected to CC (the status of the F and R
terminals is ignored). Use
to set the Jog Frequency and use
to select the Jog Stop Method.
26 — Forced Jog Reverse — This setting initiates a Forced Reverse Jog when connected to CC. The Forced Reverse Jog
command provides a reverse-run signal so long as this terminal is connected to CC (the status of the F and R terminals is
ignored). Use
to set the Jog Frequency and use
to select the Jog Stop Method.
www
. ElectricalPartManuals
. com
Содержание Adjustable Speed Drive H7 Series
Страница 198: ...H7 ASD Operation Manual Appendix A 191 Figure 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 199: ...192 Appendix A H7 ASD Operation Manual Figure 24 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 201: ...194 Appendix A H7 ASD Operation Manual Figure 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...