H7 ASD Operation Manual
165
Analog 2 Terminal Adjustment
Program
⇒
Meter Terminal Adjustment Parameters
⇒
Analog 2
This parameter adjusts the coefficient of the circuit to obtain an output that
corresponds with a known input.
This function is used in the calibration of external signal measuring devices
(DVM, counters, etc.).
Direct Access Number — F675
Parameter Type — Numerical
Factory Default — 512
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
FP Terminal Setting
Program
⇒
Terminal Selection Parameters
⇒
FP
This parameter commands the multifunction programmable FP terminal to
monitor the value of 1 of 31 possible system functions. As the monitored
function changes in magnitude or frequency, the pulse count of the FP output
pulse train changes in direct proportion to changes in the monitored function.
As the monitored value goes up so does the pulse count of the FP output.
Note: The duty cycle of the output pulse train remains at 65 ±5.0 µS.
Possible assignments for this output terminal are listed in
.
Direct Access Number — F676
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
FP Terminal Adjustment
Program
⇒
Terminal Selection Parameters
⇒
FP
This parameter sets the full-scale reading of the FP Terminal. The full-scale
reading of the monitored variable selected in
may be set here.
Direct Access Number — F677
Parameter Type — Numerical
Factory Default — 3.840
Changeable During Run — Yes
Minimum — 1.000
Maximum — 43.200
Units — kHz
Display Units for Voltage and Current
Program
⇒
Utility Parameters
⇒
Display Units
This parameter sets the unit of measurement for current and voltage values
displayed on the EOI.
Settings:
%
V/A
Direct Access Number — F701
Parameter Type — Selection List
Factory Default — %
Changeable During Run — Yes
Hz Per User-defined Unit
Program
⇒
Utility Parameters
⇒
Display Units
This parameter allows the user to input a quantity to be displayed on the EOI
that is proportional to the output frequency of the drive.
This feature is useful when the output of a process is moved along at a rate that
is proportional to the output frequency of the drive.
Direct Access Number — F702
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.0
Units — Hz/UDU
www
. ElectricalPartManuals
. com
Содержание Adjustable Speed Drive H7 Series
Страница 198: ...H7 ASD Operation Manual Appendix A 191 Figure 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 199: ...192 Appendix A H7 ASD Operation Manual Figure 24 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 201: ...194 Appendix A H7 ASD Operation Manual Figure 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...