154
H7 ASD Operation Manual
Pattern Run #14 Run-Time Setting
Program
⇒
Pattern Run Control Parameters
⇒
Preset Speeds
⇒
14
This parameter sets the run-time value for the #14 Preset Speed mode when
used as part of a Pattern Run.
Direct Access Number — F598
Parameter Type — Numerical
Factory Default — 5
Changeable During Run — No
Minimum — 1
Maximum — 8000
Units — Seconds
Pattern Run #15 Run-Time Setting
Program
⇒
Pattern Run Control Parameters
⇒
Preset Speeds
⇒
15
This parameter sets the run-time value for the #15 Preset Speed mode when
used as part of a Pattern Run.
Direct Access Number — F599
Parameter Type — Numerical
Factory Default — 5
Changeable During Run — No
Minimum — 1
Maximum — 8000
Units — Seconds
Electronic Thermal Protection #1
Program
⇒
Motor Parameters
⇒
Motor Set #1
The Motor #1 Electronic Thermal Protection parameter specifies the motor
overload current level for motor set #1. This value is entered as either a
percentage of the full load rating of the ASD or as the FLA of the motor.
The unit of measurement for this parameter may be set to Amps or it may be set
as a percentage of the ASD rating. The name-plated FLA of the motor may be
entered directly when Amps is selected as the unit of measurement (see
to
change the display unit).
Electronic Thermal Protection settings (#1 – #4) will be displayed in Amps if
the EOI display units are set to V/A rather than %.
Direct Access Number — F600
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 10.0
Maximum — 100.0
Units — %
Overcurrent Stall Level
Program
⇒
Protection Parameters
⇒
Stall
This parameter specifies the output current level at which the output frequency
is reduced in an attempt to prevent a trip. The overcurrent level is entered as a
percentage of the maximum rating of the drive.
Direct Access Number — F601
Parameter Type — Numerical
Factory Default — (drive dependent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.0
Units — %
www
. ElectricalPartManuals
. com
Содержание Adjustable Speed Drive H7 Series
Страница 198: ...H7 ASD Operation Manual Appendix A 191 Figure 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 199: ...192 Appendix A H7 ASD Operation Manual Figure 24 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 201: ...194 Appendix A H7 ASD Operation Manual Figure 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...