H7 ASD Operation Manual
11
I/O and Control
The ASD can be controlled by several input types and combinations thereof, as well as operate within a
wide range of output frequency and voltage levels. This section discusses the ASD control methods and
supported I/O functions.
The Control Terminal Strip supports discrete and analog I/O functions and is shown in
.
lists the names, the default settings, and the descriptions of the input and output terminals of
the Control Terminal Strip PWA.
Note:
To use the input control lines of the Control Terminal Strip the Command Mode
setting must be set to Use Control Terminal Strip (Program
⇒ Fundamental
Parameters
⇒
Standard Mode Selection
⇒ Command Mode ⇒ Use Control
Terminal Strip).
shows the basic connection diagram for the H7 system.
Table 2. Control Terminal Strip default assignment terminal names and functions.
Default
Term. Setting
Input/Output
Default Function
Circuit Config.
ST
Discrete Input
Standby (jumper to CC to operate the unit) — Multifunctional
programmable discrete input (see
for further
information on this terminal).
RES
Discrete Input
Reset — Multifunctional programmable discrete input.
F
Discrete Input
Forward — Multifunctional programmable discrete input.
R
Discrete Input
Reverse — Multifunctional programmable discrete input.
S1
Discrete Input
Preset Speed 1 — Multifunctional programmable discrete input.
S2
Discrete Input
Preset Speed 2 — Multifunctional programmable discrete input.
S3
Discrete Input
Preset Speed 3 — Multifunctional programmable discrete input.
S4
Discrete Input
Emergency Off — Multifunctional programmable discrete input.
RR
Analog Input
RR — Multifunction programmable analog input
(0.0 to 10 volt input — 0 to 80 Hz output).
RX
Analog Input
RX — Multifunctional programmable analog input
(-10 to +10 VDC input — -80 to +80 Hz output).
II
Analog Input
II — Multifunctional programmable analog input (4 [0] to 20 mADC
input — 0 to 80 Hz output) (see
for the location of
the II terminal).
VI
Analog Input
VI — Multifunctional programmable analog input
(0 to 10 VDC input — 0 to 80 Hz output).
P24
DC Output
24 VDC @ 50 mA output.
PP
DC Output
PP — 10.0 VDC voltage source for the external potentiometer.
OUT1
Discrete Output Low Frequency — Multifunctional programmable discrete output.
OUT2
Discrete Output Reach Frequency — Multifunctional programmable discrete output.
FP
Output
Frequency Pulse — an output pulse train that has a frequency which is
based on the output frequency of the ASD.
AM
Output
Produces an output current that is proportional to the magnitude of the
function assigned to this terminal (see
).
FM
Output
FLC
Output
Fault relay (common).
FLB
Output
Fault relay (N.C.).
FLA
Output
Fault relay (N.O.).
CC
—
Control common (Do Not connect to Earth Gnd).
Discrete Input Terminals
⇒
On = connected to CC.
www
. com
Содержание Adjustable Speed Drive H7 Series
Страница 198: ...H7 ASD Operation Manual Appendix A 191 Figure 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 199: ...192 Appendix A H7 ASD Operation Manual Figure 24 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 201: ...194 Appendix A H7 ASD Operation Manual Figure 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...