H7 ASD Operation Manual
Communication Reference Adjust
Program
⇒
Communication Setting Parameters
⇒
Communication
Reference Adjust
This parameter selects the communications reference for scaling.
See
for further information on this setting.
Scaling the communications signal is not required for all applications.Settings:
Disabled
Common Serial (TTL)
RS232/485
Communication Card
Direct Access Number — F810
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Communications Reference Setpoint #1 (%)
Program
⇒
Communication Setting Parameters
⇒
Communication
Reference Adjust
, this parameter is used to allow the user to set the gain
and bias of the speed control input to the drive when the speed control signal is
received via the source selected at
.
Gain and Bias Settings
When operating in the Speed Control mode and using one of the control
sources from Settings above, the settings that determine the gain and bias
properties of the input signal are:
•
Communications Reference Speed Setpoint #1
),
•
the communications input signal value that represents Communications
Reference Speed Setpoint #1
(frequency)
,
•
Communications Reference Speed Setpoint #2
(frequency)
), and
•
the communications input signal value that represents Communications
Reference Speed Setpoint #2
(frequency)
.
Once set, as the input signal value changes, the output frequency of the drive
will vary in accordance with the above settings.
This parameter sets the Communications Reference input value that represents
Communications Reference Speed Setpoint #1 (frequency). This value is
entered as 0 to 100% of the Communications Reference input value range.
Direct Access Number — F811
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100.0
Units — %
Communications Speed Setpoint #1 (frequency)
Program
⇒
Communication Setting Parameters
⇒
Communication
Reference Adjust
This parameter is used to set the gain and bias of the Communications
Reference speed control input.
See
for further information on this setting.
This parameter sets Communications Reference Speed Setpoint #1.
Direct Access Number — F812
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (
)
Units — Hz
www
. ElectricalPartManuals
. com
Содержание Adjustable Speed Drive H7 Series
Страница 198: ...H7 ASD Operation Manual Appendix A 191 Figure 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 199: ...192 Appendix A H7 ASD Operation Manual Figure 24 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 201: ...194 Appendix A H7 ASD Operation Manual Figure 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...