Micro-Master Touch User Guide
42
© 2014 Toro Australia Pty Ltd
Ver 1.2, June 2014
cycle. If the PreStart Delay is set, the PreSet Delay is executed for each cycle.
Control Inputs
The Micro-Master Touch controller includes a large array of control sensor inputs to control irrigation.
The available inputs include switch inputs, analogue 4-20mA sensors, flow meters (analogue, pulse,
or aggregate), and rules.
Switch inputs are considered valid when closed.
Analogue Sensors are considered valid when the measured value exceeds the set alarm value for
the sensor.
Analogue, Pulse, and Aggregate Flow Meters are considered valid when the measured flow exceeds
the set alarm value for the flow meter.
Rules are considered valid when all of the input conditions for the rule are met.
Start Sensor
The Start Sensor will start irrigation when valid.
Stop Sensor
The Stop Sensor stops the current irrigation when valid.
Hold Sensor
The Hold Sensor will hold (pause) the current irrigation for the time the hold sensor is valid.
Skip Sensor
If the Skip Sensor becomes valid, the current program will stop the current group or station and
progress (skip) to the next group or station. The program will continue to skip while the Skip Sensor
is valid. If the number of skips exceeds the Skip Count, the irrigation is stopped.
Pump Set
Each program can have it's own Pump Set. Pumps Sets can be either a Pump Set from the Pump
system, a single station program, or an output on the front panel.
Filter Bank
Each program can have it's own Filter Bank.
Flow Meter
Each program can have it's own Flow Meter.