Document Ref 942583-001 Rev 8
Page 5-31
Quantium 510 Installation Manual
Installation
5.6.1
JUNCTION BOX WIRING
During the removal or replacement of the M2000T Junction Box cover, the
machined flame path of the cover and the junction box should be inspected for
damage. If any defects or scratches are found then the junction box and/or
cover must be replaced - this is essential for product safety. Once removed,
always store the cover in a safe place.
Note : The correct tightening torque for the junction box cover is 18Nm.
Three different sizes of cable gland entries are available from Tokheim for the
M2000T Junction Box:-
• For cable sizes 6-11mm
• For cables sizes 10-13mm
• For cable sizes 14-17mm
Ensure that the correct gland size is chosen to suit each installation cable. Failure
to do so will compromise product safety.
The special requirements relating to the use of the M2000T Junction box are:-
• Gland size 6-11mm must be tightened to a torque of 114Nm
• Gland size 10-13mm must be tightened to a torque of 35Nm
• Gland size 14-17mm must be tightened to a torque of 70Nm
• Ensure that all cables terminating in the M2000T Junction Box are securely
fastened to the dispenser frame adjacent to the box.
The wiring in the main junction box will vary according to different models and
options. The drawings in this section show the Tokheim recommended installation
but differences may exist in the standards relating to installation in different
countries and local regions, in which case the local and/or national standards
must be employed.