2.3.2. 24 V Emergency cutoff input settings (DIP switch 8 operation) (SX-2000AO only)
The 24 V Emergency cutoff input can be set to be enabled or disabled.
Once enabled when the SX-2000 system is combined with an emergency broadcast system, a 24 V DC is
normally kept being supplied to this 24 V emergency cutoff input terminal and is cut off (24 V emergency cutoff
function) in emergency situations. This interrupts the general-purpose broadcast from the SX-2000, allowing
the emergency broadcast to override it. At the same time, the EMERGENCY indicators flash, one on the
SX-2000SM's front panel and others in the fluorescent displays on the front panels of SX-2000AOs in 24 V
emergency cutoff state.
Note
When using this input terminal in combination with an emergency broadcast system, set DIP switch 8 to ON.
Step 1. Remove the protective cover on the SX-2000AO's front panel by unscrewing it with a Phillips screwdriver.
01234
5678
9AB
CD
EF
01234
5678
9AB
CD
EF
Protective cover
Screw
DIP switch
Reset key
Inside of the protective cover
Step 2. Set the DIP switch.
2-1. If using the 24 V emergency cutoff input, set DIP switch 8 to ON.
2-2. If not using the 24 V emergency cutoff input, set DIP switch 8 to OFF.
Step 3. Replace the protective cover.
Note: Switch 8 is set to OFF
by default.
ON
1 2 3 4 5 6 7 8
ON
1 2 3 4 5 6 7 8