MEC 320 GENSET CONTROLLER
PM079 Rev 0 07/06/08 91 Thomson Technology
Mains setup
6500 Mains power
No.
Setting
Min. setting
Max. setting Factory
setting
6501 Mains power
Day
-20000 kW
20000 kW
750 kW
6502 Mains power
Night
-20000 kW
20000 kW
1000 kW
6503 Mains power
Transducer max
0 kW
20000 kW
1500 kW
6504 Mains power
Transducer min
-20000 kW
0 kW
-1500 kW
6510 Daytime period
The period outside the daytime period is defined as the nighttime period.
No.
Setting
Min. setting
Max. setting Factory
setting
6511 Daytime period
Start hour
0 h
23 h
8 h
6512 Daytime period
Start minute
0 min
59 min
0 min
6513 Daytime period
Stop hour
0 h
23 h
16 h
6514 Daytime period
Stop minute
0 min
59 min
0 min
6520 Start gen-set
The set point refers to the mains power set points in 6500 Mains power.
No.
Setting
Min. setting
Max. setting Factory
setting
6521 Start generator
Set point
5%
100%
80%
6522 Start generator
Timer
0.0 s
990.0 s
10.0 s
6523 Start generator
Minimum load
0%
100%
5%
6530 Stop gen-set
The set point refers to the mains power set points in 6500 Mains power.
No.
Setting
Min. setting
Max. setting Factory
setting
6531 Stop generator
Set point
0%
80%
60%
6532 Stop generator
Timer
0.0 s
990.0 s
30.0 s
6540 Test running
No.
Setting
Min. setting Max. setting Factory
setting
6541 Test
Set point
1%
100%
80%
6542 Test
Timer
0.5 min
999.0 min
5.0 min
6543 Test
Return
Semi-auto
Auto
Auto
6550 Fixed power set point
No.
Setting
Min. setting Max. setting Factory
setting
6551 Fixed power set point P set point
0%
100%
100%
Transducer max. equals 20mA, and Transducer min. equals 4mA. Both settings
must be adjusted.