MEC 320 GENSET CONTROLLER
PM079 Rev 0 07/06/08 92 Thomson Technology
6590 Mains failure voltage
No.
Setting
Min. setting Max. setting Factory
setting
6591 Mains failure U
Fail. delay
1.0 s
990.0 s
5.0 s
6592 Mains failure U
Mains OK delay
10 s
9900 s
60 s
6593 Mains failure U
Low voltage
80%
100%
90%
6594 Mains failure U
High voltage
100%
120%
110%
6595 Mains failure U
Mains fail. control Start eng. +
open MB
Start eng.
Start eng. +
open MB
6600 Mains failure frequency
No.
Setting
Min. setting Max. setting Factory
setting
6601 Mains failure f
Fail. delay
1.0 s
990.0 s
5.0 s
6602 Mains failure f
Mains OK delay
10 s
9900 s
60 s
6603 Mains failure f
Low frequency
80.0%
100.0%
95.0%
6604 Mains failure f
High frequency
100.0%
120.0%
105.0%
6610 Mains breaker control
No.
Setting
Min. setting Max. setting Factory
setting
6611 MB control
Function
Mode shift
OFF
Mode-AMF-
Mode
Mode shift
OFF
6612 MB control
Timer t
MBC
0.0 s
30.0 s
0.5 s
6613 MB control
Back synchroni-
sation
OFF
ON
OFF
6614 MB control
Sync. to mains
OFF
ON
ON