MEC 320 GENSET CONTROLLER
PM079 Rev 0 07/06/08 82 Thomson Technology
4200 VDO 105.2
No.
Setting
Min.
setting
Max.
setting
Third
setting
Factory
setting
4201 VDO 105.2
Set point
40 deg.
150 deg.
-
110 deg.
4202 VDO 105.2
Timer
0.0 s
100.0 s
-
5.0 s
4203 VDO 105.2
Relay output A R0 (none)
-
R0 (none)
4204 VDO 105.2
Relay output B R0 (none)
Option
dependent -
R0 (none)
4205 VDO 105.2
Enable
OFF
ON
RUN
OFF
4206 VDO 105.2
Fail class
Alarm (1) Trip MB (6) -
Trip/stop (4)
4210 VDO 106.1
No.
Setting
Min.
setting
Max.
setting
Third
setting
Factory
setting
4211 VDO 106.1
Set point
0%
100%
-
10%
4212 VDO 106.1
Timer
0.0 s
100.0 s
-
10.0 s
4213 VDO 106.1
Relay output A R0 (none)
-
R0 (none)
4214 VDO 106.1
Relay output B R0 (none)
Option
dependent -
R0 (none)
4215 VDO 106.1
Enable
OFF
ON
RUN
OFF
4216 VDO 106.1
Fail class
Alarm (1) Trip MB (6) -
Warning (2)
4220 VDO 106.2
No.
Setting
Min.
setting
Max.
setting
Third
setting
Factory
setting
4221 VDO 106.2
Set point
0%
100%
-
5%
4222 VDO 106.2
Timer
0.0 s
100.0 s
-
10.0 s
4223 VDO 106.2
Relay output A R0 (none)
-
R0 (none)
4224 VDO 106.2
Relay output B R0 (none)
Option
dependent -
R0 (none)
4225 VDO 106.2
Enable
OFF
ON
RUN
OFF
4226 VDO 106.2
Fail class
Alarm (1) Trip MB (6) -
Trip/stop (4)
4300 Running detection
This set point is used to define the level where the gen-set is recognised as running. When this
RPM level is reached, the automatic running detection is enabled (6150 Running status).
Also take notice of the menu ‘remove starter’ set point (6160 Remove starter).
No.
Setting
Min. setting Max. setting Factory
setting
4301 Running detection Set point
1 RPM
4000 RPM
1000 RPM
4302 Running detection Type
Frequency detection
X
Running detection Type
Tacho
Running detection Type
Binary input
Running detection Type
Engine I/F communication
4310 Overspeed 1
No.
Setting
Min. setting Max. setting Factory
setting
4311 Overspeed 1
Set point
1 RPM
4000 RPM
1450 RPM
4312 Overspeed 1
Timer
0.0 s
100.0 s
5.0 s
4313 Overspeed 1
Relay output A
R0 (none)
R0 (none)
4314 Overspeed 1
Relay output B
R0 (none)
Option
dependent
R0 (none)
4315 Overspeed 1
Enable
OFF
ON
OFF
4316 Overspeed 1
Fail class
Alarm (1)
Trip MB (6)
Warning (2)