MEC 320 GENSET CONTROLLER
PM079 Rev 0 07/06/08 79 Thomson Technology
3310 Running feedback (binary input 115)
No.
Setting
Min.
setting
Max.
setting
Third
setting
Factory
setting
3311 Run. feedback Timer
0.0 s
180.0 s
-
10.0 s
3312 Run. feedback Relay output A
R0 (none)
-
R0 (none)
3313 Run. feedback Relay output B
R0 (none)
Option
dependent
-
R0 (none)
3314 Run. feedback Enable
OFF
ON
RUN
OFF
3315 Run. feedback Fail class
Alarm (1)
Trip MB (6) -
Warning (2)
3316 Run. feedback Type
N/O
N/C
-
N/O
3320 Ext. engine failure (binary input 116)
No.
Setting
Min.
setting
Max.
setting
Third
setting
Factory
setting
3321 Engine failure
Timer
0.0 s
180.0 s
-
10.0 s
3322 Engine failure
Relay output A R0 (none)
-
R0 (none)
3323 Engine failure
Relay output B R0 (none)
Option
dependent -
R0 (none)
3324 Engine failure
Enable
OFF
ON
RUN
OFF
3325 Engine failure
Fail class
Alarm (1)
Trip MB (6) -
Shutdown (5)
3326 Engine failure
Type
N/O
N/C
-
N/O
3330 Ext. emergency stop (binary input 117)
No.
Setting
Min.
setting
Max.
setting
Third
setting
Factory
setting
3331 Emergency STOP Timer
0.0 s
60.0 s
-
0.0 s
3332 Emergency STOP Relay output A
R0 (none)
-
R0 (none)
3333 Emergency STOP Relay output B
R0 (none)
Option
dependent -
R0 (none)
3334 Emergency STOP Enable
OFF
ON
RUN
OFF
3335 Emergency STOP Fail class
Alarm (1) Trip MB (6) -
Shutdown (5)
3336 Emergency STOP Type
N/O
N/C
-
N/O
3340 Dig. input no. 118
No.
Setting
Min.
setting
Max.
setting
Third
setting
Factory
setting
3341 Dig. input no. 118 Timer
0.0 s
100.0 s
-
10.0 s
3342 Dig. input no. 118 Relay output A
R0 (none)
-
R0 (none)
3343 Dig. input no. 118 Relay output B
R0 (none)
Option
dependent -
R0 (none)
3344 Dig. input no. 118 Enable
OFF
ON
RUN
OFF
3345 Dig. input no. 118 Fail class
Alarm (1) Trip MB (6) -
Warning (2)
3346 Dig. input no. 118 Type
N/O
N/C
-