MEC 320 GENSET CONTROLLER
PM079 Rev 0 07/06/08 83 Thomson Technology
4320 Overspeed 2
No.
Setting
Min. setting Max. setting Factory
setting
4321 Overspeed 2
Set point
1 RPM
4000 RPM
1750 RPM
4322 Overspeed 2
Timer
0.0 s
100.0 s
1.0 s
4323 Overspeed 2
Relay output A
R0 (none)
R0 (none)
4324 Overspeed 2
Relay output B
R0 (none)
Option
dependent
R0 (none)
4325 Overspeed 2
Enable
OFF
ON
OFF
4326 Overspeed 2
Fail class
Alarm (1)
Trip MB (6)
Shutdown (5)
4370 Wire failure analogue input 98
No.
Setting
Min. setting Max. setting Factory
setting
4371 W. fail. ana. 98
Output A
R0 (none)
R0 (none)
4372 W. fail. ana. 98
Output B
R0 (none)
Option
dependent
R0 (none)
4373 W. fail. ana. 98
Enable
OFF
ON
OFF
4374 W. fail. ana. 98
Fail class
Alarm (1)
Trip MB (6)
Warning (2)
4380 Wire failure analogue input 100
No.
Setting
Min. setting Max. setting Factory
setting
4381 W. fail. ana. 100
Output A
R0 (none)
R0 (none)
4382 W. fail. ana. 100
Output B
R0 (none)
Option
dependent
R0 (none)
4383 W. fail. ana. 100
Enable
OFF
ON
OFF
4384 W. fail. ana. 100
Fail class
Alarm (1)
Trip MB (6)
Warning (2)
4390 Wire failure analogue input 102
No.
Setting
Min. setting Max. setting Factory
setting
4391 W. fail. ana. 102
Output A
R0 (none)
R0 (none)
4392 W. fail. ana. 102
Output B
R0 (none)
Option
dependent
R0 (none)
4393 W. fail. ana. 102
Enable
OFF
ON
OFF
4394 W. fail. ana. 102
Fail class
Alarm (1)
Trip MB (6)
Warning (2)
4410 Wire failure VDO input 104
No.
Setting
Min. setting Max. setting Factory
setting
4411 W. fail. VDO 104
Max.
60%
100%
100%
4412 W. fail. VDO 104
Min.
0%
40%
0%
4413 W. fail. VDO 104
Output A
R0 (none)
R0 (none)
4414 W. fail. VDO 104
Output B
R0 (none)
Option
dependent
R0 (none)
4415 W. fail. VDO 104
Enable
OFF
ON
OFF
4416 W. fail. VDO 104
Fail class
Alarm (1)
Trip MB (6)
Warning (2)
4420 Wire failure VDO input 105
No.
Setting
Min. setting Max. setting Factory
setting
4421 W. fail. VDO 105
Max.
60%
100%
100%
4422 W. fail. VDO 105
Min.
0%
40%
0%
4423 W. fail. VDO 105
Output A
R0 (none)
R0 (none)
4424 W. fail. VDO 105
Output B
R0 (none)
Option
dependent
R0 (none)
4425 W. fail. VDO 105
Enable
OFF
ON
OFF
4426 W. fail. VDO 105
Fail class
Alarm (1)
Trip MB (6)
Warning (2)
Содержание MEC 320