MEC 320 GENSET CONTROLLER
PM079 Rev 0 07/06/08 80 Thomson Technology
Analogue input setup
4090 4…20mA input 98.1
No.
Setting
Min.
setting
Max.
setting
Third
setting
Factory
setting
4091 4…20mA input 98.1 Set point
4mA
20mA
-
10mA
4092 4…20mA input 98.1 Timer
0.0 s
600.0 s
-
120.0 s
4093 4…20mA input 98.1 Relay output A R0 (none)
-
R0 (none)
4094 4…20mA input 98.1 Relay output B R0 (none)
Option
dependent -
R0 (none)
4095 4…20mA input 98.1 Enable
OFF
ON
RUN
OFF
4096 4…20mA input 98.1 Fail class
Alarm (1) Trip MB (6) -
Warning (2)
4100 4…20mA input 98.2
No.
Setting
Min.
setting
Max.
setting
Third
setting
Factory
setting
4101 4…20mA input 98.2 Set point
4mA
20mA
-
10mA
4102 4…20mA input 98.2 Timer
0.0 s
600.0 s
-
120.0 s
4103 4…20mA input 98.2 Relay output A R0 (none)
-
R0 (none)
4104 4…20mA input 98.2 Relay output B R0 (none)
Option
dependent -
R0 (none)
4105 4…20mA input 98.2 Enable
OFF
ON
RUN
OFF
4106 4…20mA input 98.2 Fail class
Alarm (1) Trip MB (6) -
Warning (2)
4110 Oil pressure 1 (4…20mA input 100.1)
No.
Setting
Min.
setting
Max.
setting
Third
setting
Factory
setting
4111 Oil pressure 1
Set point
0 bar
50 bar
-
10 bar
4112 Oil pressure 1
Timer
0.0 s
180.0 s
-
5.0 s
4113 Oil pressure 1
Relay output A R0 (none)
-
R0 (none)
4114 Oil pressure 1
Relay output B R0 (none)
Option
dependent -
R0 (none)
4115 Oil pressure 1
Enable
OFF
ON
RUN
OFF
4116 Oil pressure 1
Fail class
Alarm (1) Trip MB (6) -
Warning (2)
4120 Oil pressure 2 (4…20mA input 100.2)
No.
Setting
Min.
setting
Max.
setting
Third
setting
Factory
setting
4121 Oil pressure 2
Set point
0 bar
50 bar
-
10 bar
4122 Oil pressure 2
Timer
0.0 s
180.0 s
-
5.0 s
4123 Oil pressure 2
Relay output A R0 (none)
-
R0 (none)
4124 Oil pressure 2
Relay output B R0 (none)
Option
dependent -
R0 (none)
4125 Oil pressure 2
Enable
OFF
ON
RUN
OFF
4126 Oil pressure 2
Fail class
Alarm (1) Trip MB (6) -
Warning (2)
The input is not configurable in the peak shaving mode, load takeover mode and
mains power export, because it is used as a mains power input.
The input is not configurable in the peak shaving mode, load takeover mode and
mains power export, because it is used as a mains power input.