10.2.
Remote Communication Wiring
All communication interconnecting wiring to/from the CIM Module shall
utilize #22 AWG-8 wire, twisted, shielded cable with RJ45 connectors.
All remote communication wiring outside the control panel must be run in
separate conduit and shall not be located near AC power cables to
prevent pick-up of induced voltages.
10.3.
Dielectric Testing
Do not perform any high voltage dielectric testing on the CIM connected
in the circuit as serious damage will occur to the module.
10.4.
Mounting Location/Installation
The CIM Module is designed for mounting directly onto a control panel
inner sub-panel. Considerations should be given for the following:
The controller should be installed in a dirt free, dry location away from
extreme heat sources. Adequate space should be provided around the
CIM module for control wiring.
10.5.
Mounting Dimensions
The CIM mounting dimensions are shown in the following diagram:
150 mm
190 mm
95mm
95 mm
54.5mm
54.5mm
109mm
200mm
4 HOLES
Ø 4.77mm.
(.188 in.)
DRAWING SCALE: .6:1
G:/R&D/PRODUCTS/ICS/DESIGN/CIM/102910.VSD Rev. 1 98-12-04
ENCLOSURE DEPTH: 50mm