SECTION 2
THS 2000 SOFTWARE PROGRAM
PM055 Rev 2 00/08/31
Thomson Technology
16
SECTION 2
THS 2000 SOFTWARE PROGRAM
1. Introduction
The THS 2000 software program remotely controls and monitors a Thomson Technology
(
www.
thomsontechnology.com) generator/transfer-switch control system. The THS 2000
program operates on an IBM-compatible Personal Computer with Microsoft Windows 95™,
Microsoft Windows 98™, Microsoft Windows NT™ 4.0 or Microsoft Windows 2000 operating
systems (
www.microsoft.com
). The THS 2000 program uses a TTI designed protocol to
communicate to TTI generator control system site. A site consists of a single Communication
Interface Module (CIM) and one or more associated Remote Terminal Unit (RTU) controllers.
The THS 2000 software is designed to allow a direct connection (via RS-232, RS-422 or RS-
485) to Port 2 of the CIM or a remote connection (via a host PC modem) with the internal
modem of the CIM on Port 1. The host PC modem must already be configured before
attempting a remote connection. See the operating-system help for installing and configuring
modems.
Version 3.1 of the THS2000 is intended for operation with version 3.0 of the CIM, but also
provides support for previous versions of the CIM.
Throughout this document, text that looks like
this for filenames
and other computer-type
text; text that appears in menus, dialog boxes and buttons looks like
this windows-type text
.
1.1.
Definitions
CIM
Communications Interface Module; the communications hub for a site
Dialog box
interactive window allowing the user to view or change settings
MEC 20
Microprocessor Engine Controller
Modbus
industry-standard serial automation protocol defined by Modicon
(
www.modicon.com
), part of Schneider Automation, Inc.
RTU
Remote Terminal Unit; in this context, a MEC 20 or a TSC 800
TSC 800
Transfer Switch Controller
Site
a CIM and one or more connected RTUs
Site-list
the site-list is the list of remote sites, primarily used for auto-answer and
multiple CIM sites