SECTION 3
CIM PROTOCOL
PM055 Rev 2 00/08/31
Thomson Technology
55
Port#3
Bitrate
40289 120 1 enum
0=57600, 1=38400,
2=19200, 3=14400, 4=9600,
5=4800, 6=2400, 7=1200
Port#3
Bits/char
40290
121
1
uint8 7 to 8 (8)
Port#3
Stopbits
40291
122
1
uint8 1 to 2 (1)
Port#3
Parity
40292 123 1 enum
0=Odd, 1=Even, 2=None,
3=Mark, 4=Space
Port#3 Rx
Timeout
40293
124
1
uint16 0 to 65535 (40)
Port#3 Line
Protocol
40294 125 1 enum
0=RS-232, 1=RS-422,
2=RS-485
The Modbus Configuration table is used specifically to assign a node address (CIM ID)
to the individual CIM unit. This is used in multiple CIM configurations. The CIM's are
slaves to any device connected to Port 2. However the CIM acts like a Master to
anything connected to Port 3. Communication to the individual MEC 20's will be done by
communicating to the CIM.
9.
CIM General Configuration
Field
Register
(decimal)
Address
(hex)
Register
Count
Data
Format
Value
CIM ID
40321
140
1
uint8
0 to 255 (1)
CIM response
delay (ms)
40322
141
1
uint16 0 to 5000 (30)
Poll bounds
40323
142
1
struct
see below
Call out enable
40324
143
1
boolean
0=disabled,
1=enabled
Call out mode
40325
144
1
enum
0=connect once,
1=connect to all
The CIM ID is only used for programming CIM features, it is transparent when
communicating with MEC 20's or TSC 800's.
The Poll Bounds structure has the following format: