TC 816 Operation Manual
THERMON…The Heat Tracing Specialists
®
Page 32 of 42
Operation Manual 0503 E TC 816
4.2.8
Parameter P08:
MAX OUTP
This Parameter is:
•
Valid for Temperature Controller Zones
- Zones 1 through 16
- unit in: %
•
Not valid for
Limiter Zones
•
Not valid for
Current Zones
Set point
MAX OUTP
of parameter P08 determines the maximum controller power output for the heat
tracing circuit, in case the control mode P18
CTRL MODE
is set to PID control. In no case the controller
will not allow more power than this percentage of the full scale.
The full scale power output is what the heat tracing circuit would dissipate in case the supply voltage would
not be cycled, thus stay ON all time.
Adjustment thresholds: 0...100
Default value:
100
4.2.9
Parameter P09:
AV OUTP
This Parameter is:
•
Valid for Temperature Controller Zones
- Zones 1 through 16
- unit in: %
•
Not valid for
Limiter Zones
•
Not valid for
Current Zones
Parameter P09 can not be set, only monitored. This parameter gives the average power output (
AV OUTP
)
in % of full scale over the past period of automatic operation.
Range:
0...100
Default value:
not applicable
4.2.10
Parameter P10:
OFFSET
This Parameter is:
•
Valid for Temperature Controller Zones
- Zones 1 through 16
- unit in: °C or °F
•
Valid for Limiter Zones
- Zones 1 through 16
- unit in: °C or °F
•
Valid for Current Zones
- Zones 17 through 32
- unit in: 0,1 x A => value of 10 means 1 A
Parameter P10 allows field tuning of temperature and current by adjusting the
OFFSET
.
Range:
-50...+50
Default value:
0