TC 816 Operation Manual
THERMON…The Heat Tracing Specialists
®
Operation Manual 0503 E TC 816
Page 31 of 42
4.2.7
Parameter P07:
MAN OUTP
This Parameter is:
•
Valid for Temperature Controller Zones
- Zones 1 through 16
- unit in: %
•
Not valid for
Limiter Zones
•
Not valid for
Current Zones
Set point
MAN OUTP
of parameter P07 determines the power output in % in case Parameter P06:
OP
MODE
is set to “1” (manual operation). See chapter 4.2.6.
The TC 816 regulates power output by switching ON and OFF (cycling) the supply voltage within a certain
cycle time (parameter P25
CYCL TIME
).
In order to choose the best set point you could consult parameter P09
AV OUTP
. This parameter gives
the average power output in % of full scale over the past period of automatic operation.
Adjustment thresholds: 0...100
Default value:
0