Refrigeration Maintenance
10-14
NOTE: If the low side will not pump down into a vacuum, the hot gas solenoid, or the receiver tank pressure check valve
may be stuck open. See the individual component tests for more information.
6. Continue pumping down the low side until it reaches a 25 in. Hg vacuum (-85 kPa), then turn the unit Off.
7. The low side pressure should remain below a 15 in. Hg vacuum (-51 kPa) for 2 minutes or more.
• If the low side pressure rises to 0 psig (0 kPa) and stops, there is probably a leak to the atmosphere. Check the low side for
leaks.
• If the low side pressure rises above 0 psig (0 kPa) and continues to rise (until it eventually equalizes with the high side
pressure), there is probably a leak from the high side to the low side through one (or more) of the following components:
hot gas solenoid, receiver tank pressure check valve, or the discharge valve plates in the compressor. Check the
temperatures of the refrigeration lines on each side of these components by hand. There is often a temperature difference
between the two sides of a leaking component. See the individual component tests for more information.
8. Back seat the receiver tank outlet valve. Perform a “Refrigerant Gauge Removal” procedure.
LOW SIDE PUMP DOWN RECIPROCATING COMPRESSOR
Operate the unit in cool for 10 minutes before performing the low side pump down.
1. Attach a gauge manifold to the suction service valve and the discharge service valve.
2. Operate the unit in high speed cool.
3. Front seat the receiver tank outlet valve and allow the low side to pump down to a 15 in. Hg vacuum (-51 kPa).
4. Turn the unit Off.
5. Prepare to perform service on the low side by raising the low side pressure through the gauge manifold to 1 to 2 psig (7 to 14
kPa).
6. Back seat the receiver tank outlet valve. Perform a “Refrigerant Gauge Removal” procedure.
LOW SIDE PUMP DOWN SCROLL COMPRESSOR
CAUTION: Do not pull scroll compressor into a vacuum below 10 in. Hg vacuum (-34 kPa) to perform routine maintenance
procedures.
NOTE: Operate the unit in cool for 2 to 5 minutes before performing the low side pump down.
1. Attach a gauge manifold to the suction service valve and the discharge service port. Attach another low pressure gauge to the
suction access port located in the suction line near the accumulator inlet. Low loss fittings must be used on the hoses connected
to the discharge service port and the suction access port.
2. Operate the unit in low speed cool.
3. Front seat the receiver tank outlet valve and allow the low side to pump down to 0 to 5 in. Hg vacuum (0 to -17 kPa).
CAUTION: Do not run scroll compressor in a vacuum for more than 1 minute.
NOTE: To check certain components, front seat the suction service valve to isolate the low side while it is still in a vacuum.
See “Refrigeration System Checks” and the individual component tests for more information.
4. Turn the unit Off.
5. Prepare to perform service on the low side by raising the low side pressure through the gauge manifold to 1 to 2 psig (7 to 14
kPa).
6. Front seat the suction service valve to isolate the low side. The discharge check valve in the compressor is an imperfect seal
and will not keep the discharge pressure from leaking back through the compressor. Use the suction access port located near
the accumulator inlet to access the low side for leak testing and evacuation.
7. Back seat the suction service valve and then the receiver tank outlet valve. Perform a “Refrigerant Gauge Removal”
procedure.
R-404A/R-452A/R-134A
These units use R-404A/R-452A (R-134A - T-Dairy). This refrigerant is classified as a Hydro-fluorocarbon (HFC) because it
contains hydrogen fluorine and carbon. It does not contain chlorine.
Содержание T-1000R
Страница 14: ...Safety Precautions 2 6 Warning Decals 2e24151g0 ...
Страница 18: ...Specifications 3 4 ENGINE CLUTCH Engagement 600 100 RPM Dynamic Torque 66 fT lb 89 5 N m minimum 1600 RPM ...
Страница 34: ...Maintenance Inspection Schedule 4 10 ...
Страница 57: ...Unit Description 5 23 Purge Mode UT Series 1 3 4 5 2 ...
Страница 67: ...Unit Description 5 33 Zone 1 Cool and Zone 2 Cool UT SPECTRUM Units ...
Страница 69: ...Unit Description 5 35 Purge Mode UT SPECTRUM Units ...
Страница 71: ...Unit Description 5 37 Zone 1 Cool and Zone 2 Heat UT SPECTRUM Units ...
Страница 72: ...Unit Description 5 38 ...
Страница 74: ...Diesel Electric Menu 6 28 Adjust Brightness 6 29 Time 6 30 ...
Страница 120: ...Operating Instructions Standard HMI 7 18 ...
Страница 152: ...Engine Maintenance 9 14 T Series Fuel and Oil System Components TK 376 ...
Страница 154: ...Engine Maintenance 9 16 T Series Fuel and Oil System Components TK 270 ...
Страница 156: ...Engine Maintenance 9 18 UT Series Fuel System Components AMA768 ...
Страница 172: ...Engine Maintenance 9 34 T Series Engine Mounting Components for 2 Cylinder Engine ...
Страница 184: ...Engine Maintenance 9 46 ...
Страница 238: ...Refrigeration Maintenance 10 54 ...
Страница 246: ...Clutch Maintenance 11 8 ...
Страница 258: ...Structural Maintenance 12 12 ...
Страница 264: ...Mechanical Diagnosis 13 6 ...
Страница 265: ...14 Electric Standby Diagnosis ...
Страница 268: ...Electric Standby Diagnosis 14 4 ...
Страница 269: ...15 Refrigeration System Diagnosis ...
Страница 272: ...Refrigeration System Diagnosis 15 4 ...
Страница 280: ...Remote Evaporators 16 8 ...
Страница 282: ...Wiring Diagrams and Wiring Schematics 17 2 ...