49
9.2.4 E3/F5: Fan Speed Out of Control Error
Condition: Indoor fan speed stays too low (300 RPM) for a certain time.
Possible Causes: - Wiring mistake
- Fan assembly faulty
- Fan motor faulty
- PCB faulty
Power off, then restart the
unit 2 minutes later
Shut off the power supply,
Rotate the fan by hand.
The unit operates normally.
Find out the cause and have
it solved
Check the wiring of fan
motor
No
Yes
No
Correct the connections.
No
No
Replace the fan motor
Yes
Yes
Measure the voltage for the
fan motor from the main
PCB
Yes
Replace the main PCB
No
See next page for index 1
Содержание 12H47YIMI
Страница 10: ...10 1080 mm 226 mm 335 mm 30H48ZIMI 49 57 1259 mm 11 1 282 mm 14 25 362 mm 36H46ZIMI...
Страница 19: ...19 Model Voltage V Capacity BTU Type 12H47ZOMI 230 12 000 HEAT PUMP...
Страница 20: ...20 Model Voltage V Capacity BTU Type 18H47ZOMI 230 18 000 HEAT PUMP 24H46ZOMI 230 24 000 HEAT PUMP...
Страница 21: ...21 Model Voltage V Capacity BTU Type 30H48ZIMI 230 30 000 HEAT PUMP 36H46ZIMI 230 36 000 HEAT PUMP...
Страница 55: ...55 Note The pictures below are only for reference they may be not same as the ones on your unit P U P V...
Страница 56: ...56 P W N U...
Страница 57: ...57 N V N W...
Страница 82: ...82 7 Then lift the PCB assembly off the unit NOTE All wires are still connected...