9.2.6 EC: Refrigerant Leak Detection
Condition: T
C
: Temperature of the evaporator coil at the moment of startup
During the first five (5) minutes of starting up, if T2 < T
C
- 3.8°F (2°C) does not
hold for four (4) continuous seconds three (3) times.
Possible Causes:
- T2 sensor faulty
- Indoor PCB faulty
- Refrigerant system faulty (i.e. leakage/blockage)
Is there any blocking? (Such as the
capillary or the welded points of the pipes)