61
9.2.10 P4: Inverter Compressor Drive Error
Condition: An abnormal inverter compressor drive is detected by a special detection
circuit, including communication signal detection, voltage detection, compressor rotation
speed signal detection, etc.
Possible Causes:
- Wiring mistake
- IPM malfunction
- Outdoor fan assembly faulty
- Compressor malfunction
- Outdoor PCB faulty
For 9K to 24K units
Please refer to the section 9.3.4.
Replace motor if it fails.
Check if the compressor resistance values
are uniform. Refer to Section 9.3.1.
Refer to Section 9.3.3.