9.2.8 P0: IPM Malfunction or IGBT Over-current Protection
Condition: The voltage signal that the IPM sends to the compressor drive chip is
abnormal.
Possible Causes:
- Wiring mistake
- IPM malfunction
- Outdoor fan assembly faulty
- Compressor malfunction
- Outdoor PCB faulty
For 9K to 24K units
Check the wiring between main PCB
and compressor
Correct the connection or replace
the wires and connectors.
Yes
No
Check the IPM
No
Yes
Replace the IPM board or replace
the main PCB
Check the outdoor fan and the
outdoor unit ventilation
No
Please refer to the solution of
【
Fan
Speed Has Been Out Of Control
】
malfunction
Yes
Check the compressor resistance
values
No
Replace the compressor.
Yes
Replace the outdoor main PCB
Refer to Section 9.3.1.
Please refer to the section 9.3.4.
Replace motor if it fails.
Check the IPM. Refer to Section 9.3.3.