9.2.8 P1: High or Low Voltage Protection
Condition: An abnormal voltage rise or drop was detected by the specified voltage
detection circuit.
Possible Causes:
- Power supply faulty
- Refrigerant system faulty (i.e. leakage/blockage)
- PCB faulty
Check the power supply
Check the connections and
wires
Stop the unit
No
Yes
No
Correct the connections or
replace the wires.
Yes
Replace the reactor
Yes
No
Replace the IPM board
Check the voltage between P
and N
Check the reactor
Yes
No
Replace outdoor main PCB
Measuring the DC Voltage between P and N Port
The normal voltage value should be around 310V.
P
N
Check the voltage between P
and N. Refer to the section 9.3.5.