46
9.2.2 E1: Indoor/Outdoor Communication Error
Condition: Indoor unit does not receive feedback from outdoor unit for 110 seconds, and
this repeats four times continuously.
Possible Causes:
- Wiring mistake
- Indoor or outdoor PCB faulty
Measure Vs, is it positive fluctuation?
(Vs is the voltage between S and N of
outdoor unit. Red pan-S, Black pan-N)
Measure Vs, is it positive fluctuation?
(Vs is the voltage between S and N of
outdoor unit. Red pan-S, Black pan-N)
Yes
Power off, then restart the unit 2 minutes later
Power off, then restart the unit 2 minutes later
No
Replace the outdoor main PCB.
Power on. Is the error
extinguished?
Replace the outdoor main PCB.
Power on. Is the error
extinguished?
Check the outdoor wiring connection
Check the outdoor wiring connection
Replace the indoor main PCB.
Power on. Is the error
extinguished?
Replace the indoor main PCB.
Power on. Is the error
extinguished?
Yes
Replace the outdoor main PCB.
Replace the outdoor main PCB.
No
Replace the indoor main PCB.
Replace the indoor main PCB.
No
Check the indoor wiring connection
Check the indoor wiring connection
Yes
Yes
Check whether reactor
is normal?
Check whether reactor
is normal?
Yes
Replace the reactor
Replace the reactor
No
*Vs is the voltage between 2 and 3.
See next page for “Testing the Voltage” and “Testing the Reactor”.
Содержание 12H47YIMI
Страница 10: ...10 1080 mm 226 mm 335 mm 30H48ZIMI 49 57 1259 mm 11 1 282 mm 14 25 362 mm 36H46ZIMI...
Страница 19: ...19 Model Voltage V Capacity BTU Type 12H47ZOMI 230 12 000 HEAT PUMP...
Страница 20: ...20 Model Voltage V Capacity BTU Type 18H47ZOMI 230 18 000 HEAT PUMP 24H46ZOMI 230 24 000 HEAT PUMP...
Страница 21: ...21 Model Voltage V Capacity BTU Type 30H48ZIMI 230 30 000 HEAT PUMP 36H46ZIMI 230 36 000 HEAT PUMP...
Страница 55: ...55 Note The pictures below are only for reference they may be not same as the ones on your unit P U P V...
Страница 56: ...56 P W N U...
Страница 57: ...57 N V N W...
Страница 82: ...82 7 Then lift the PCB assembly off the unit NOTE All wires are still connected...