8.4.3.4 Defrost Mode
After extended use, frost may build up on the coils on the outdoor unit. The development
of frost can slow the rate of heat transfer which can cause many various problems such
as overloading the system. To prevent this, the system has an automatic defrost mode
according to the temperature T3, and also the compressor running time.
During the defrosting mode, the compressor keep running, indoor and outdoor motor will
stop, the operating symbol
“
”
will be displayed on the indoor panel.
If any one of the following items is satisfied, the defrosting will finish and the machine will
back to normal heating mode.
----T3 rises to be higher than TCDE 1.8
°
F.
----T3 keeps on being higher than TCDE 3.6
°
F for 80 seconds.
----The machine has run for 15 minutes in defrosting mode.
8.4.3.5 Evaporator temperature protection
Off: Compressor stops.
Decrease: Decrease the running frequency to the lower
level.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
8.4.4 AUTO Mode
This mode can be chosen with remote controller and the setting temperature can be changed
between 62°F~86°C
In Auto mode, the unit will automatically choose between cooling, heating, or fan-only mode
according to the temperature
difference ΔT (ΔT = T1 –
T
S
) on the auto-fan speed. If the
temperature changes enough to switch between heating and cooling mode, the compressor will
stop for 15 minutes first and then determine what mode to switch into according to ΔT.
Indoor fan will run
at auto fan of the relevant mode.
The
louver
operates same as in relevant
mode.
Range
Mode
ΔT >
3.6°F
COOL
-3.6
°F < ΔT ≤
3.6°F
FAN
ΔT ≤
-3.6°F
HEAT
TEstop
T2
Resume
Off
Decrease
TEdown
TEH2
Hold
TEstop
T2
Resume
Off
Decrease
TEdown
TEH2
Hold
Содержание 12H47YIMI
Страница 10: ...10 1080 mm 226 mm 335 mm 30H48ZIMI 49 57 1259 mm 11 1 282 mm 14 25 362 mm 36H46ZIMI...
Страница 19: ...19 Model Voltage V Capacity BTU Type 12H47ZOMI 230 12 000 HEAT PUMP...
Страница 20: ...20 Model Voltage V Capacity BTU Type 18H47ZOMI 230 18 000 HEAT PUMP 24H46ZOMI 230 24 000 HEAT PUMP...
Страница 21: ...21 Model Voltage V Capacity BTU Type 30H48ZIMI 230 30 000 HEAT PUMP 36H46ZIMI 230 36 000 HEAT PUMP...
Страница 55: ...55 Note The pictures below are only for reference they may be not same as the ones on your unit P U P V...
Страница 56: ...56 P W N U...
Страница 57: ...57 N V N W...
Страница 82: ...82 7 Then lift the PCB assembly off the unit NOTE All wires are still connected...