48
9.2.3 E2: Zero-Crossing Detection Error
Condition: When PCB does not receive the zero crossing signal feedback for four (4)
minutes or the zero crossing signal time interval is abnormal.
Possible Causes:
- Wiring mistake
- PCB faulty
Check if the connections and
power supply is normal?
Correct the connections. Turn on the
unit when the power supply is good.
No
Yes
Indoor main PCB is
defective. Replace indoor
main PCB.