112
Value range
Adjustable values
0.05 - 10
Standard value, suitable for most applications.
0.3
Adjustment of the detector brightness actual value
Procedure:
1. Determine the lux values below the presence detector with the lux meter
2. Brightness actual value is read from the detector
3. Compare lux values
4.
Change and send room correction factor (table 1)
5. Brightness actual value is read from the detector
6.
Compare lux value and if necessary repeat the procedure
Table 1
for higher detector brightness actual value
→
select lower room correction factor
for lower detector brightness actual value
→
select higher room correction factor
Setting limits
Set the room correction factor in such a way that
room correction factor x brightness actual value is between 5 lx and 13,000 lx.