102
N N L L A
P P S1
H2
PlanoCentro
101-A-230V
H1
N
L
N N L L
P P
PlanoCentro
000-A-230V
Slave
Master
4.3 Master-Slave parallel circuit operation
Several detectors switch one lighting group
●
The Master switches the lighting. All other detectors are slaves.
●
Presence detection through all detectors together.
●
Light measurement only with master.
●
Parameter only with master.
●
Maximum of 10 detectors can be connected in parallel.
●
Use the same phase for all detectors.
Presence
(e.g. HVAC)
Master: PlanoCentro 101-A-230V
Slave: PlanoCentro 000-A-230V