6.1 Adjustment with the remote control
Parameters are sent to the presence detector via infrared with the SendoPro. The parameters can
be read-out before changes take place. Changed parameters are immediately accepted and ap
-
plied by the detector.
LED
Description
Flickering during
3 sec
After pressing the send function on the management remote control, the presence detector
displays correct receiving by flickering for 3 sec
lights up shortly
The command/parameter sent from the management remote control via infrared is rejected by the pres
-
ence detector. The command is not valid. Check the selected detector type and the sent parameters.
6.2 Operation mode
The PlanoCentro has 3 operation modes
●
Normal
●
Test presence (page 118)
●
Test light (page 120)
6.3 Function mode
The function type only influences channel A light.
Fully automatic:
Lighting switches on and off automatically. (Based on presence, absence and brightness)
auto
Semi-automatic:
Switching on must always be done manually. The presence detector automatically switches
it off. (Based on absence or brightness). Response with parallel signals see page .
man
6.4 Staircase lightning function
Manual switching on and off possible.
Off
The presence detector is used as staircase time switch. Manual switching off with push-buttons or SendoClic
is not possible.
On