4.2 General parallel connecting
The parallel signal is sent via P-terminal and also received. Every detector, regardless of whether
it is master or slave, sends the presence signal via P-terminal. Thus, one master and one slave as
well as two masters can be connected together with the parallel signal. See following chapter
with parallel connecting variations.
-
The parallel signal is compatible with the compact range.
-
The parallel signal is basically included for the light and presence channel.
Parallel signal response
Fully automatic
function mode
The parallel signal is included for the light and presence output. Parallel signals are incorpo-
rated for adaptable switch-off delay time light.
Semi-automatic
function mode
The parallel input signal only activates the H presence channel (HVAC). The channel A light
has to be switched on via push-button or switch.
Once channel H presence (HVAC) and channel A light are switched on, the will be continu
-
ously triggered with parallel signals.
Room monitoring
Information about room monitoring is also transmitted with the parallel signal.
!
CAUTION!
Power supply:
Detectors linked to one another via the parallel signal have to be connected
to the same phase.