56
5-7-7. Various status signals (CV, CC & ALARM)
It is possible to check the status using the open collector output.
■
Constant-voltage (CV) status signal
This status signal goes Low when the PSF Series power supply unit
enters the constant-voltage (CV) status.
■
Constant-current (CC) status signal
This status signal goes Low when the PSF Series power supply unit
enters the constant-current (CC) status.
■
Alarm status signal
This status signal goes Low when the PSF Series power supply unit
enters the alarm status.
PC3H7 made by SHARP
Item
Symbol
Max. rating
Unit
Output
Collector-emitter voltage
V
CEO
66
V
Emitter-collector voltage
V
ECO
6
V
Collector current
I
C
50
mA
Collector loss
P
C
150
mW
Total allowable loss
P
T
170
mW
Isolation voltage
BV
S
2500
Vrms
CHA
:
Constant-voltage (CV) status: Pins 23 and 26 (COM)
Constant-current (CC) status: Pins 24 and 26 (COM)
Alarm status: Pins 25 and 26 (COM)
CHB
:
Constant-voltage (CV) status: Pins 4 and 1 (COM)
Constant-current (CC) status: Pins 3 and 1 (COM)
Alarm status: Pins 2 and 1 (COM)
26
EXT CONT 「J3」
1
2
25
CV
CC
ALARM
CHA
status
26
EXT CONT 「J3」
1
2
25
CV
CC
ALARM
CHB
status
Inside of PSF
Series
Fig.5-19 Status Terminals
Содержание PSF-1200L
Страница 5: ......
Страница 11: ...2 400W 2 Channel Type PSF 400L2 400W Type PSF 400L 800W Type PSF 800L 800W Type For Current Extention PSF 800LS...
Страница 18: ...9...
Страница 115: ...106 PSF 800LS Dust filter Dust filter Front grill Front grill Pull frontward while pressing here...
Страница 117: ...108 290 35 7 6 5 82 7 209 9 10 9 124 The handle is available by option Fig 11 2 Outside Dimensions of PSF 800LS...
Страница 121: ...7F Towa Fudosan Shin Yokohama Bldg 2 18 13 Shin Yokohama Kohoku ku Yokohama Kanagawa 222 0033 Japan http www texio co jp...