5–12 Retransmit
An air-conditioned room uses two TEC-2500 units to control the temperature and humidity. The temperature and
humidity must be recorded on a chart recorder. The preferred ranges for these two parameters are: 20°C to 30°C and
40% RH to 60% RH. The recorder inputs accept a 0–5V signal.
To achieve this, set the following parameters in the setup menu.
UNIT 1:
UNIT 2:
FUNC=FULL
FUNC=FULL
COM=0–5V
COMM=0–5V
AOFN=PV1
AOFN=PV1
AOLO=20.0(°C)
AOLO=40.0(%)
AOHI=30.0(°C)
AOHI=60.0(%)
IN1=PTDN
IN1=0–1V (according to humidity sensor)
IN1U=°C
IN1U=PU
DP1=1-DP
DP1=1-DP
SP1L and SP1H are used to limit the adjustment range of the set point.
Содержание TEC-2500
Страница 2: ...NOTES...
Страница 4: ...NOTES...
Страница 10: ...6...
Страница 11: ...7 1 5 Menu Overview...
Страница 13: ...9 1 7 Parameter Description...
Страница 14: ...10...
Страница 16: ...12...
Страница 17: ...13...
Страница 18: ...14...
Страница 19: ...15...
Страница 20: ...16 NOTES...
Страница 25: ...21 2 9 CT Heater Current Input Wiring...
Страница 27: ...23 2 11 Output 1 Wiring Continued...
Страница 29: ...25...
Страница 31: ...27 2 14 Alarm 2 Wiring...
Страница 32: ...28 2 15 RS 485...
Страница 34: ...30 2 17 Analog Retransmission...
Страница 35: ...31 2 18 Programming Port See figure 1 3 in section 1 3 to find the programming port location...
Страница 36: ...32 NOTES...
Страница 45: ...41 Although the above descriptions are based on alarm 1 the same conditions can be applied to alarm 2...
Страница 94: ...90 NOTES...
Страница 96: ...92...
Страница 97: ...93...
Страница 98: ...94 NOTES...
Страница 101: ...97 A 1 Menu Existence Conditions...
Страница 102: ...98...
Страница 103: ...99...
Страница 104: ...100 A 2 Factory Menu Description...
Страница 105: ...101 A 5 Memo Use the following table as a master copy for your settings page 1 of 2...
Страница 106: ...102...