3–17 Failure Transfer
The controller will enter failure mode if one of the following conditions occurs:
1.
SB1E
occurs (due to input 1 sensor break or input 1 current below 1mA if
4–20mA is selected or input 1 voltage below 0.25V if 1–5V is selected) if PV1,
P1-2, or P2-1 is selected for PVMD or PV1 is selected for SPMD.
2.
SB2E
occurs (due to input 2 sensor break or input 2 current below 1mA if
4–20mA is selected or input 2 voltage below 0.25V if 1–5V is selected) if PV2,
P1-2, or P2-1 is selected for PVMD or PV2 is selected for SPMD.
3.
ADER
occurs if the A-D converter of the controller fails.
Output 1 and output 2 will perform the failure transfer function as one of the
following conditions occurs:
1. During power starts (within 2.5 seconds).
2. The controller enters failure mode.
3. The controller enters manual mode.
4. The controller enters calibration mode.
Output 1 failure transfer, if activated, will perform:
1. If output 1 is configured as proportional control (PB1
≠
0), and BPLS is selected
for O1FT, then output 1 will perform bumpless transfer. Thereafter, the
previous averaging value of MV1 will be used for controlling output 1.
2. If output 1 is configured as proportional control (PB1
≠
0), and a value of 0 to
100.0% is set for O1FT, then output 1 will perform failure transfer. Thereafter,
the value of O1FT will be used for controlling output 1.
3. If output 1 is configured as ON-OFF control (PB1
≠
0), then output 1 will be
driven OFF if O1FN selects REVR and be driven ON if O1FN selects DIRT.
Output 2 failure transfer, if activated, will perform:
1. If COOL is selected for OUT2, and BPLS is selected for O1FT, then output 2
will perform bumpless transfer. Thereafter, the previous averaging value of
MV2 will be used for controlling output 2.
2. If COOL is selected for OUT2, and a value of 0 to 100.0 % is set for O2FT,
then output 2 will perform failure transfer. Thereafter, the value of O1FT will be
used for controlling output 2.
Alarm 1 failure transfer
is activated as the controller enters failure mode.
Thereafter, alarm 1 will transfer to the ON or OFF state preset by A1FT.
Exception:
If A1FN is configured for loop break (LB) alarm or sensor break
(SENB) alarm, alarm 1 will be switched to ON state independent of the setting of
A1FT. If A1FN is configured for dwell timer (TIMR), alarm 1 will not perform failure
transfer.
Alarm 2 failure transfer
is activated as the controller enters failure mode.
Thereafter, alarm 2 will transfer to the ON or OFF state preset by A2FT.
Exception:
If A2FN is configured for loop break (LB) alarm or sensor break
(SENB) alarm, alarm 2 will be switched to ON state independent of the setting of
A2FT. If A2FN is configured for dwell timer (TIMR), alarm 2 will not perform failure
transfer.
Failure mode occurs as:
1. SB1E
2. SB2E
3. ADER
Failure Transfer of output 1 and
output 2 occurs as:
1. Power start (within 2.5 seconds)
2. Failure mode is activated
3. Manual mode is activated
4. Calibration mode is activated
Failure Transfer of alarm 1 and alarm
2 occurs as:
Failure mode is activated
Failure Transfer Setup:
1. O1FT
2. O2FT
3. A1FT
4. A2FT
Содержание TEC-2500
Страница 2: ...NOTES...
Страница 4: ...NOTES...
Страница 10: ...6...
Страница 11: ...7 1 5 Menu Overview...
Страница 13: ...9 1 7 Parameter Description...
Страница 14: ...10...
Страница 16: ...12...
Страница 17: ...13...
Страница 18: ...14...
Страница 19: ...15...
Страница 20: ...16 NOTES...
Страница 25: ...21 2 9 CT Heater Current Input Wiring...
Страница 27: ...23 2 11 Output 1 Wiring Continued...
Страница 29: ...25...
Страница 31: ...27 2 14 Alarm 2 Wiring...
Страница 32: ...28 2 15 RS 485...
Страница 34: ...30 2 17 Analog Retransmission...
Страница 35: ...31 2 18 Programming Port See figure 1 3 in section 1 3 to find the programming port location...
Страница 36: ...32 NOTES...
Страница 45: ...41 Although the above descriptions are based on alarm 1 the same conditions can be applied to alarm 2...
Страница 94: ...90 NOTES...
Страница 96: ...92...
Страница 97: ...93...
Страница 98: ...94 NOTES...
Страница 101: ...97 A 1 Menu Existence Conditions...
Страница 102: ...98...
Страница 103: ...99...
Страница 104: ...100 A 2 Factory Menu Description...
Страница 105: ...101 A 5 Memo Use the following table as a master copy for your settings page 1 of 2...
Страница 106: ...102...