3–11 Deviation Band Alarm
A deviation band alarm presets two reference levels relative to set point. Two
types of deviation band alarm can be configured for alarm 1 and alarm 2. These
are deviation band high alarm (A1FN or A2FN select DB.HI) and deviation band
low alarm (A1FN or A2FN select DB.LO). If alarm 2 is required, then select AL2
for OUT2. Now NONE can't be selected for A2FN, otherwise
Er06
will appear.
A1SP and A1HY are hidden if alarm 1 is selected as a deviation band alarm.
Similarly, A2SP and A2HY are hidden if alarm 2 is selected as a deviation band
alarm.
The trigger level for deviation band alarm moves with the set point. For alarm 1,
the trigger level=SP1±A1DV. For alarm 2, the trigger level=SP1±A2DV. One of
four alarm modes can be selected for alarm 1 and alarm 2. These are: normal
alarm, latching alarm, holding alarm and latching/holding alarm. See section 3-9
for descriptions of these alarm modes.
*
DBHi will trigger an alarm if the process value is outside of the deviation value (out of band)
*
DBLo will trigger an alarm if the process value is within the deviation value (in band)
Examples:
Error Code
2 types of deviation band alarms:
DB.HI, DB.LO
Deviation band alarm 1:
Setup: A1FN, A1MD
Adjust: SP1, A1DV
Trigger level=SP1±A1DV
Deviation band alarm 2:
Setup: OUT2, A2FN, A2MD
Adjust: SP1, A2DV
Trigger level=SP1±A2DV
Содержание TEC-2500
Страница 2: ...NOTES...
Страница 4: ...NOTES...
Страница 10: ...6...
Страница 11: ...7 1 5 Menu Overview...
Страница 13: ...9 1 7 Parameter Description...
Страница 14: ...10...
Страница 16: ...12...
Страница 17: ...13...
Страница 18: ...14...
Страница 19: ...15...
Страница 20: ...16 NOTES...
Страница 25: ...21 2 9 CT Heater Current Input Wiring...
Страница 27: ...23 2 11 Output 1 Wiring Continued...
Страница 29: ...25...
Страница 31: ...27 2 14 Alarm 2 Wiring...
Страница 32: ...28 2 15 RS 485...
Страница 34: ...30 2 17 Analog Retransmission...
Страница 35: ...31 2 18 Programming Port See figure 1 3 in section 1 3 to find the programming port location...
Страница 36: ...32 NOTES...
Страница 45: ...41 Although the above descriptions are based on alarm 1 the same conditions can be applied to alarm 2...
Страница 94: ...90 NOTES...
Страница 96: ...92...
Страница 97: ...93...
Страница 98: ...94 NOTES...
Страница 101: ...97 A 1 Menu Existence Conditions...
Страница 102: ...98...
Страница 103: ...99...
Страница 104: ...100 A 2 Factory Menu Description...
Страница 105: ...101 A 5 Memo Use the following table as a master copy for your settings page 1 of 2...
Страница 106: ...102...