3–13 Loop Break Alarm
A1FN selects LB if alarm 1 is required to act as a loop break alarm. Similarly, if
alarm 2 is required to act as a loop break alarm, then set OUT2 to AL2 and
A1FN to LB. TIME, A1SP, A1DV, and A1HY are hidden if alarm 1 is configured
as a loop break alarm. Similarly, TIME, A2SP, A2DV, and A2HY are hidden if
alarm 2 is configured as a loop break alarm.
One of four kinds of alarm modes can be selected for alarm 1 and alarm 2.
These are: normal alarm, latching alarm, holding alarm and latching/holding
alarm. However, the holding mode and latching/holding mode are not
recommended for loop break alarm since loop break alarm will not perform the
holding function even if it is set for holding or latching/holding mode. See
section 3-9 for descriptions of these alarm modes.
Loop break conditions are detected during a time interval of 2TI1 (double the
integral time, but 120 seconds maximum). Hence the loop break alarm doesn't
respond as quickly as it occurs. If the process value doesn't increase (or
decrease) while the control variable MV1 has reached its maximum (or
minimum) value within the detecting time interval, a loop break alarm (if
configured) will be activated.
Loop break alarm (if configured) occurs when any following conditions happen:
1. Input sensor is disconnected (or broken).
2. Input sensor is shorted.
3. Input sensor is defective.
4. Input sensor is installed outside (isolated from) the process.
5. Controller fails (A-D converter damaged).
6. Heater (or chiller, valve, pump, motor etc.) breaks or fails or is uninstalled.
7. Switching device (used to drive heater) is open or shorted.
Loop break alarm 1
Setup: A1FN=LB
A1MD=NORM, LTCH
Loop break alarm 2
Setup: OUT2=AL2
A2FN=LB
A2MD=NORM, LTCH
Содержание TEC-2500
Страница 2: ...NOTES...
Страница 4: ...NOTES...
Страница 10: ...6...
Страница 11: ...7 1 5 Menu Overview...
Страница 13: ...9 1 7 Parameter Description...
Страница 14: ...10...
Страница 16: ...12...
Страница 17: ...13...
Страница 18: ...14...
Страница 19: ...15...
Страница 20: ...16 NOTES...
Страница 25: ...21 2 9 CT Heater Current Input Wiring...
Страница 27: ...23 2 11 Output 1 Wiring Continued...
Страница 29: ...25...
Страница 31: ...27 2 14 Alarm 2 Wiring...
Страница 32: ...28 2 15 RS 485...
Страница 34: ...30 2 17 Analog Retransmission...
Страница 35: ...31 2 18 Programming Port See figure 1 3 in section 1 3 to find the programming port location...
Страница 36: ...32 NOTES...
Страница 45: ...41 Although the above descriptions are based on alarm 1 the same conditions can be applied to alarm 2...
Страница 94: ...90 NOTES...
Страница 96: ...92...
Страница 97: ...93...
Страница 98: ...94 NOTES...
Страница 101: ...97 A 1 Menu Existence Conditions...
Страница 102: ...98...
Страница 103: ...99...
Страница 104: ...100 A 2 Factory Menu Description...
Страница 105: ...101 A 5 Memo Use the following table as a master copy for your settings page 1 of 2...
Страница 106: ...102...