3–14 Sensor Break Alarm
Alarm 1 or alarm 2 can be configured as a sensor break alarm by selecting
SENB for A1FN or A2FN. If alarm 2 is required as a sensor break
alarm, then AL2 should be selected for OUT2. The sensor break alarm is
activated as soon as failure mode occurs. Refer to section 3-17 for failure mode
conditions. Note that A-D failure also creates a sensor break alarm. TIME,
A1SP, A1DV, and A1HY are hidden if alarm 1 is configured as a sensor break
alarm. Similarly, TIME, A2SP, A2DV and A2HY are hidden if alarm 2 is
configured as a sensor break alarm.
One of four kinds of alarm modes can be selected for sensor break alarm.
These are: normal alarm, latching alarm, holding alarm, and latching/holding
alarm. However, the holding alarm and latching/holding alarm are not
recommended for the sensor break alarm since the sensor break alarm will not
perform the holding function even if it is set for holding or latching/holding
mode. See section 3-9 for the descriptions of these alarm modes.
3–15 SP1 Range
SP1L (SP1 low limit value) and SP1H (SP1 high limit value) in the setup menu
are used to confine the adjustment range of SP1.
Example:
A freezer is working in its normal temperature range -10°C to -15°C.
In order to avoid an abnormal set point, SP1L and SP1H are set with the
following values:
SP1L=-15°C
SP1H=-10°C
Now SP1 can only be adjusted within the range of -10°C to -15°C.
Sensor Break Alarm 1
Setup:
A1FN=SENB
A1MD=NORM, LTCH
Hidden:
TIME, A1SP, A1DV, A1HY
Sensor Break Alarm 2
Setup:
OUT2=AL2
A2FN=SENB
A2MD=NORM, LTCH
Hidden:
TIME , A2SP, A2DV, A2HY
Setup :
SP1L, SP1H
Содержание TEC-2500
Страница 2: ...NOTES...
Страница 4: ...NOTES...
Страница 10: ...6...
Страница 11: ...7 1 5 Menu Overview...
Страница 13: ...9 1 7 Parameter Description...
Страница 14: ...10...
Страница 16: ...12...
Страница 17: ...13...
Страница 18: ...14...
Страница 19: ...15...
Страница 20: ...16 NOTES...
Страница 25: ...21 2 9 CT Heater Current Input Wiring...
Страница 27: ...23 2 11 Output 1 Wiring Continued...
Страница 29: ...25...
Страница 31: ...27 2 14 Alarm 2 Wiring...
Страница 32: ...28 2 15 RS 485...
Страница 34: ...30 2 17 Analog Retransmission...
Страница 35: ...31 2 18 Programming Port See figure 1 3 in section 1 3 to find the programming port location...
Страница 36: ...32 NOTES...
Страница 45: ...41 Although the above descriptions are based on alarm 1 the same conditions can be applied to alarm 2...
Страница 94: ...90 NOTES...
Страница 96: ...92...
Страница 97: ...93...
Страница 98: ...94 NOTES...
Страница 101: ...97 A 1 Menu Existence Conditions...
Страница 102: ...98...
Страница 103: ...99...
Страница 104: ...100 A 2 Factory Menu Description...
Страница 105: ...101 A 5 Memo Use the following table as a master copy for your settings page 1 of 2...
Страница 106: ...102...