iRIS8 - Addressable Fire Alarm Panel
– Installer Programming
8
1.3.2. LED Indication for Activated Zones
The LED indication for activated zones is available on the front panel for zone numbers from 1 to 200. The zone number
is lighting or blinking according the type of the generated fire alarm together with the status LEDs of the panel.
GENERAL FIRE ALARM
One or several zones can be in alarm mode after fire or
evacuation event in the system. The numbers of activated
zones are lighting on in red together with the GENERAL
FIRE system status LED.
PRE ALARM Condition
The pre-alarm condition is applied for zones set in 2Devices
or DOUBLE operation mode. The numbers of activated
zones are blinking in red and the PRE ALARM and
WARNING system status LEDs are lighting on.
TEST Condition
Testing of the zones is possible from Access Levels 2 and 3.
The system status LED TEST is lighting on. In case of
activation of zone in test mode, its number is lighting on in
red. There is no indication for general fire or pre-alarm event.
Performing of zone testing is described in details in item
Note: The disabled for operation zones do not report for fire, faults, evacuation or test events. If DISABLE system status
LED is lighting on, you can review the type of the disablements (including zones disablements) in Events Reviewing
mode on the TFT screen.
The LED indication for zones can be tested for operation at Maintenance menus
1.3.3. TFT Screen
There are different active sections for operation on the iRIS8 screen at Access Level 3. The available interface elements
have the following meaning.
1
– Status Icons Section.
2
– Section for reviewing the current active
events for iRIS8 panel and the other
connected fire panels in the network.
3
– Section with Operation buttons.
4
– Section with Functional buttons.
1.3.4. Status Icons Section
In the status section are presented the current time and date, and a dynamic field with icons showing the current status
of iRIS8 fire alarm panel. The icons are changing according the status for Alarm, Fault, Disable or Reset active events.
The Alarm indication is with the highest priority.