iRIS8 - Addressable Fire Alarm Panel
– Installer Programming
41
Enter INPUTS submenu.
By default, all Inputs are set as NONE Type.
Use the arrow buttons, or enter an input number from 1 to
250. Press the active button for selection the input type
(NONE).
Note:
The screen content may change according
the settings for Input Type.
The different input types are available for section in a list.
The type, as the other specific settings must be confirmed
in the main screen with APPLY button. Select the input
type to load the specific parameters for setting.
Periphery
This type is selected, when the input is an input terminal of the main input-output module of
the panel.
Loop
This type is selected, when the input is an input terminal of a loop device, as MIO-22,
MIO-22M, MIO-40, MINP M, etc.
Zone
This option is selected, when the input will be activated from a zone event.
Alarms
This option is selected, when the input will be activated from an encountered number of
alarms.
Time
This option is selected, when the input will be activated on a time schedule.
Date
This option is selected, when the input will be activated at a time period.
Action
This option is selected, when the input will be activated from an action event.
General
This option is selected, when the input will be activated from a general event.
Network
This option is selected, when the input will be activated from a network device
(panel/repeater number).
Zone Group
This option is selected, when the input will be activated from a zone in fire alarm or fault,
included in a group.
Device Group
This option is selected, when the input will be activated from a device included into a group.
NONE
The input is not used.
All Input types have some common settings available in the main settings screen. The settings are described in the
following table:
Note
This is an active text field for description for the input up to 40 symbols. For text entering
see item
Behavior
This setting is for behaviour of the input in case of activation. Every pressing of the button
changes the setting.
LATCHED
- Once activated, the input stays active until RESET.
UNLATCHED
- Monitors the status.
Polarity
This setting is for the input active status. Every pressing of the button changes the setting.
- NORMAL
- The input is ON when receiving of activation signal (event)
and will is OFF
(normal status) when the signal is lost.
- INVERTED -
The input is ON when the signal is lost, and is OFF (normal status) when
receiving of activation signal (event).
Input Delay
Set a time delay for activation of the input within the interval 0
–600 sec.
The common setting for all Input Types is selecting a Group number. The inputs can be organized to groups
according their operation.
Note: By default, the Input 1 is set to Group 1, Input 2 is set to Group 2, etc. The installer can reorganize the Group
numbers according the system requirement and configuration.